20
4.2
Connect Network Surge protection
Connect a 10 base-T / 100 base-T network cable to the RJ-45 network
surge protection “IN” jack on the rear of the UPS. Connect from the “OUT”
jack with network cabling to network equipment.
4.3
Connect Computer Interface Port
Connect the supplied interface cable (RS-232 or USB, Optional)
between the interface port on the rear of the UPS and the computer
interface port. See software installation guide in the CD-ROM (Optional) for
installation purpose.
21
4.4
REPO Switch
The UPS is equipped with an Emergency Power Off (EPO) switch. The
user must supply a means of interfacing with the EPO circuit to allow
disconnecting the UPS input feeder breaker to interrupt all sources of
power to the UPS and connected equipment to comply with national and
local wiring codes and regulations.
1 2
1 = REPO+
2 = Ground
Short Pin 1 and Pin 2 to enable the REPO function