6. Menu
SETPOINTS
IPR96D Ground Protection Relay
6.8
Instruction Manual: IPR96D GBM 24/11/2020
Calibration Mode
Test BLE
Value
No
RANGE: Yes; No
Choose YES and press
ENTER
, to carry out a test.
Calibration Mode
Digital Input1
Value
DEACTIVATED
This screen shows the status of the Digital Input 1 (activated or deactivated).
Calibration Mode
Digital Input2
Value
DEACTIVATED
This screen shows the status of the Digital Input 2 (activated or deactivated).
Calibration Mode
Test Relays
Value
None
RANGE: NONE; TRIP; AUX1; AUX2; ALL
Energize one or more output relays.
During the test, the chosen relay(s) will remain energized for five (5) seconds
and the navigation will be disabled throughout this time.
Calibration Mode
Device ID
Value
63aDedRt2f4=
A code like the example on the screen uniquely identifies the IPR96D.
It is useful in case the password gets lost or in case Orion Italia requires it for
technical support.
The following screens will only be visible if the system is accessed with the Second-Level Password (PSW2):
See [APPENDIX A]
Calibration Mode
K Time
Value
0
RANGE: -116
116
STEPS: 1
It allows the application of a corrective K to the relay clock to correct the time
drift.
Consult Orion Italia for further information.
Any modification applied to the following settings, can affect metering and protection functions.