6. Menu
SETPOINTS
IPR96D Ground Protection Relay
6.4
Instruction Manual: IPR96D GBM 24/11/2020
Ground Protect.
Ground Timed2 O/C
Pickup
Value
12 %CT
RANGE: 1
300
STEPS: 1
Enter the ground overcurrent pickup level. This level determines the current level
at which the relay will start counting the circuit breaker/disconnector trip time
according to the protection curve selected in the following line:
GROUND O/C
CURVE
.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground Timed2 O/C Relay
≠
- - -
Ground Protect.
Ground O/C Curve
Value
ANSI MOD INV
RANGE: ANSI EXTREME INV; ANSI VERY INV; ANSI NORMAL INV; ANSI MOD
INV; DEFINITE TIME; IEC-C EXTREME INV; IEC-B VERY INV; IEC-A NORMAL
INV; IEC SHORT TIME; IAC EXTREME INV; IAC VERY INV; IAC NORMAL INV;
IAC MODERATE INV
Enter the ground 2 overcurrent protection curve shape required.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground Timed2 O/C Relay
≠
- - -
Ground Protect.
Ground Timed2 O/C
Delay
Value
1.00 s
RANGE: 0.01
600
STEPS: 0.01, 0.1, 1
Enter the ground timed 2 overcurrent delay. The related output will activate if the
current rating is superior to “GROUND TIMED O/C PICKUP” for a longer time than
the set one.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground O/C Curve = DEFINITE TIME
and
≠ - - -
Ground Protect.
Ground Timed2 O/C
Mult.
Value
1.0
RANGE: 0.1
20.0
STEPS: 0.1
Set the ground overcurrent multiplier for the selected curve.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground Timed2 O/C Relay
≠
- - -
Ground Protect.
Ground Inst. O/C
Relay
Value
- - -
RANGE: NONE; ANY COMBINATION OF TRIP, AUX1 OR AUX2.
Select the outputs to be activated by the ground instantaneous overcurrent
protection (ANSI 50N).
Ground Protect.
Ground Inst. O/C
Pickup
Value
120 %CT
RANGE: 1
2000
STEPS: 1, 10
Enter the instantaneous overcurrent pickup level. This level determines the
current level at which the relay will start counting the time for the activation of the
related output.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground Inst. O/C Relay
≠
- - -
Ground Protect.
Ground Inst. O/C
Delay
Value
0 ms
RANGE: 0
2000
STEPS: 10
Enter the intervention delay for ground instantaneous overcurrent protection.
If: the ground current increases above the value entered in “GROUND INST. O/C
PICKUP” for a time > delay time selected, the output will activate.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground Inst. O/C Relay
≠
- - -
6.5 Setpoints: DIGITAL INPUT
Digital Input
Input 1 Function
Value
NONE
RANGE: ACTIVATE AUX2; ACTIVATE AUX1; EXTERNAL RESET; BREAKER
STATUS; NONE
Select the function to be associated with INPUT 1.