6. Menu
SETPOINTS
IPR96D Ground Protection Relay
6.3
Instruction Manual: IPR96D GBM 24/11/2020
Date & Time
2018. Jan. 9
16:54:02:00
Enter Password
- - - -
Insert the First-Level password (PSW1) to set or modify Date and Time.
To store new Date and Time:
1.
Insert the correct password, if required, using
▲ and ▼
2.
If the password is correct, the year will blink.
Date & Time
2018. Jan. 9
16:54:02:00
Value
2018. Jan. 9
16:54:02:00
3.
Select the year using
▲ and ▼ and press
ENTER
.
4.
Repeat steps 2 and 3 for month, day, hour, minutes, and seconds.
5.
Press
ENTER
to store the new date and time.
Note: press
ENTER
, the decimals of the seconds will begin from zero (0).
6.4 Setpoints: GROUND PROTECTION
Ground Protect.
Ground Timed1 O/C
Relay
Value
- - -
RANGE: NONE; ANY COMBINATION OF TRIP, AUX1 OR AUX2.
Select the outputs to be activated by the ground timed 1 overcurrent protection
(ANSI 51.1 N/G).
Ground Protect.
Ground Timed1 O/C
Pickup
Value
12 %CT
RANGE: 1
300
STEPS: 1
Enter the ground overcurrent pickup level. This level determines the current level
at which the relay will start counting the circuit breaker/disconnector trip time
according to the protection curve selected in the following line:
GROUND O/C
CURVE
.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground Timed1 O/C Relay
≠
- - -
Ground Protect.
Ground O/C Curve
Value
ANSI MOD INV
RANGE: ANSI EXTREME INV; ANSI VERY INV; ANSI NORMAL INV; ANSI MOD
INV; DEFINITE TIME; IEC-C EXTREME INV; IEC-B VERY INV; IEC-A NORMAL
INV; IEC SHORT TIME; IAC EXTREME INV; IAC VERY INV; IAC NORMAL INV;
IAC MODERATE INV
Enter the ground 1 overcurrent protection curve shape required.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground Timed1 O/C Relay
≠
- - -
Ground Protect.
Ground Timed1 O/C
Delay
Value
1.00 s
RANGE: 0.01
600
STEPS: 0.01, 0.1, 1
Enter the ground timed 1 overcurrent delay. The related output will activate if the
current rating is superior to “GROUND TIMED O/C PICKUP” for a longer time than
the set one.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground O/C Curve = DEFINITE TIME
and
≠ - - -
Ground Protect.
Ground Timed1 O/C
Mult.
Value
1.0
RANGE: 0.1
20.0
STEPS: 0.1
Set the ground overcurrent multiplier for the selected curve.
[6.4
Setpoints: GROUND PROTECT.
]
If Ground Timed1 O/C Relay
≠
DEFINITE
TIME or - - -
Ground Protect.
Ground Timed2 O/C
Relay
Value
- - -
RANGE: NONE; ANY COMBINATION OF TRIP, AUX1 OR AUX2.
Select the outputs to be activated by the ground timed 2 overcurrent protection
(ANSI 51.2 N/G).