90 | USER MANUAL
OMX 103UNI
12.
TECHNICAL DATA
INPUT
No. of inputs
1 or 2, isolated
DC
Range
±90 mA
< 200 mV
Input 1
±180 mA
< 200 mV
Input 1
±30 mV
> 10 MΩ
Input 3
±60 mV
> 10 MΩ
Input 3
±1000 mV
> 10 MΩ
Input 3
±20 V
1,25 MΩ
Input 2
±40 V
1,25 MΩ
Input 2
±80 V
1,25 MΩ
Input 2
PM
Range
±5 mA
< 200 mV
Input 1
±20 mA
< 200 mV
Input 1
4...20 mA
< 200 mV
Input 1
±2 V
1 MΩ
Input 2
±5 V
1 MΩ
Input 2
±10 V
1 MΩ
Input 2
OHM
Range
0…15 Ω
0…30 Ω
0…150 Ω
0…300 Ω
0…1 kΩ
0…3 kΩ
0…15 kΩ
0…30,0 kΩ (only for 2 or 4-wire connection)
Connection
2, 3 or 4 wire
RTD
Type Pt
EU > 100/500/1 000 Ω, with 3 850 ppm/°C
Pt xxx
-50°…450°C
US > 100 Ω, with 3 920 ppm/°C
Pt 100
-50°…450°C
RU > 50/100 Ω with 3 910 ppm/°C
Pt 50
-200°…1 100°C
Pt 100
-50°…450°C
Type Ni
Ni 1 000/ Ni 10 000 with 5 000/6 180 ppm/°C
Ni xxx
-50°…250°C
Type Cu
Cu 50/Cu 100 with 4 260/4 280 ppm/°C
Cu 100/4280
-200°…200°C
Cu 100/4260
-50°…200°C
Connection
2, 3 or 4 wire
T/C
Type
J (Fe-CuNi)
-100°…900°C
K (NiCr-Ni)
-100°…1
300°C
T (Cu-CuNi)
-200°…400°C
E (NiCr-CuNi)
-100°…800°C
B (PtRh30-PtRh6)
700°…1 820°C
S (PtRh10-Pt)
100°…1
760°C
R (Pt13Rh-Pt)
100°…1 760°C
N (Omegalloy)
-0°…1 300°C
L (Fe-CuNi)
-100°…900°C
Chromel-Copel
-100°…800°C
DU
Suuply for lin. pot.
2,5 VDC/6 mA
min. R of potentiometer is 500 Ohm
PROJECTION
Display
LCD with backlight,
2x 3 char 2x description (3 characters)
Format
-99…999
Decimal point
configurable in the menu
ACCURACY
TC
50 ppm/°C
Accuracy
±0,15 % of full scale + 1 digit
±0,25 % of full scale + 1 digit
Ni 10 000
±0,3 % of full scale + 1 digit
T/C
Accuracy of CJC
±1,5°C
Rate
0,5…200 masurements/s
Overload
10x (t < 100 ms),
2x (long term)
Linearization
by linear interpolation in 177 points
- can be set only using free OM Link SW
Digital filters
Averaging, Floating average, Exponential filter,
Rounding
Comp. of leads R
max. 30 Ω
RTD
CJC
configurable
T/C
-20°...99°C or automatic
Functions
Tare - display reset
Hold - measurement suspended (at contact)
Lock - control keys disabled
MM - Min/Max value, Math functions
OM Link
company communication SW for setting, operation
and update of instrument's FW
Watch-dog
reset after 400 ms
Calibration
at 25°C and 40 % r.h.
COMPARATOR
No. of outputs
1 to 6
Type
digital, configurable in the menu,
contact closure < 50 ms
Mode
Hysteresis, From-To, Batch, Error
Limits
-99 … 999
Hysteresis
0…999
Delay
-99 … 99,9 s
Outputs
1…6x relay with NO contact (Form A)
Relay
1/8 HP 277 VAC, 1/10 HP 125 V, Pilot Duty D300
DATA OUTPUTS
No. of outputs
1 to 2
Protocols
ASCII, MESSBUS, MODBUS - RTU, PROFIBUS
Data format
8 bit + no 1 stop bit (ASCII)
Rate
600…230 400 Baud
9 600 Baud…12 Mbaud (PROFIBUS)
RS 232
isolated, 2-way communication
RS 485
isolated, 2-way communication,
address can be asigned (max. 31 devices)
PROFIBUS
SIEMENS data protocol
Ethernet
10/100BaseT, secure communication,
TCP/IP Modbus (Slave)
* values applicable to resistor load