USER MANUAL
OMX 103UNI
| 75
6.
MENU
PROFI
6.3.1d Setting Values for Limit 1 Evaluation
2s
› › › OUT. ›
› LIM. ›
› L. 1 ›
› › › › L. 1 ›
L. 1
Parameter
Display User
Setting
Description
Aplicable only for limit mode Hysteresis
HYS.
Setting limit
L. 1 values
L. 1
-99
…
999
Setting Limit 1 values
•
Range: : -99…999
•
DEF
33,3
→
→
Setting limit
L. 1 hysteresis
H.1
-99
…
999
Setting Limit 1 hysteresis
•
S p e c i f i e s t h e b a n d a r o u n d t h e l i m i t
symmetrically,
LIM.
± ½
HYS.
•
Range: -99…999
•
DEF
0,0
→
→
Setting Limit
L.1 delay
C.1
-99
…
99.9
Setting limit 1 delay
•
Positive time > limit output closes when limit
value
L.1
is exceeded and the set time
C.1
expires
•
Negative time > limit output opens when
limit value
L.1
is exceeded and the set time
C.1
expires
•
Range: -99…99,9 s
•
DEF
0,0
→
→
Aplicable only for limit mode From-To
F-T.
Setting L. 1
interval
Beginning
ON.1
-99
…
999
Setting the beginning of the interval for
switching on the Limit 1
•
Range: -99…999
→
→
Setting L. 1
interval
End
OF.1
-99
…
999
Setting the end of the interval for switching
on the Limit 1
•
Range: -99…999
→
→
Aplicable only for limit mode Batch
DOS.
Setting L.1
period
P. 1
-99
…
999
Setting the period (duration) of switching
on Limits 1
•
Range: -99…999
→
→
Setting Limit
L.1 delay
C.1
-99
…
99.9
Setting limit 1 delay
•
Positive time > limit output closes when limit
value
L.1
is exceeded and the set time
C.1
expires
•
Negative time > limit output opens when
limit value
L.1
is exceeded and the set time
C.1
expires
•
Range: -99…99,9 s
•
DEF
0,0
→
→
L. 1