12.
TECHNICAL DATA
ANALOGUE OUTPUTS
No. of outputs
1 to 4
Type
isolated, configurable with16 bit D/A converter,
type and range are selectable in the menu
Non-linearity
0,1 % of FS
TC
15 ppm/°C
Speed
response to change of value < 1 ms
Voltage ranges
0…2/5/10 V, ±10 V
Current ranges
0…5/20 mA/4…20 mA
- compensation of leads' resist. up to 600 Ω
EXCITATION
Fixed voltage
24 VDC/max. 1 W, isolated
POWER SUPPLY
Options
10…30 V AC/DC, max. 5 VA, PF ≥ 0,4,
I
STP
< 40 A/1 ms, isolated
- fuse inside (T 4000 mA)
80…250 V AC/DC, max. 5 VA, PF ≥ 0,4,
I
STP
< 40 A/1 ms, isolated
- fuse inside (T 630 mA)
MECHANICAL PROPERTIES
Material
PA 66, incombustible UL 94 V-I, blue
Dimensions
113 x 98 x 35 mm
Installation
to DIN rail 35 mm wide
OPERATING CONDITIONS
Connection
connector terminal board, conductor cross-section
<1,5 mm2 /<2,5 mm2
Stabilisation period
within 5 minutes after power-on
Operating temp.
-20°…60°C
Storage temp.
-20°…85°C
Protection
IP20
Construction
safety class I
Overvoltage cat.
EN 61010-1, A2
Dielectric strength
4 kVAC over 1 min between supply and input 4 kVAC
over 1 min. between supply and data/analogue
output
4 kVAC over 1 min. between input and relay output
2,5 kVAC over 1 min. between input and data/
analogue output
2,5 kVAC over 1 min. between inputs
Insulation resist.
for pollution degree II, measurement cat. III power
supply > 600 V (BI), 300 V (DI)
Input/Output > 600 V (BI), 300 V (DI)
EMC
EN 61326-1
Seismic resistance
IEC 980: 1993, par. 6
BI - Basic isolation, DI - Double Isolation