SPECIFICATIONS
SNAP PAC S-Series User’s Guide
52
SNAP-PAC-S2
Four serial ports that can be used as general purpose ports or for serial I/O units;
each port is software configurable as either RS-232 (Tx, Rx, COM, DTR, DCD,
RTS, CTS) or as RS-485 (2-wire, 4-wire, optional termination, optional biasing);
optional
mistic
signal interrupts
I/O unit compatibility
Ethernet-based I/O units
Serial-based I/O units
Opto 22 SNAP PAC R-series, SNAP PAC EB-series, SNAP SIO, SNAP EIO, and
SNAP UIO brains
SNAP PAC SB-series, Serial B3000, SNAP-BRS, B100/B200,
mistic
remote
bricks (G4D16R, G4D32RS, G4A8R)
Power requirements
8–32 VDC ±0.5, 11.3 VA maximum
(SNAP-PAC-S1 controllers with serial numbers below 500,000 use 8–24 VDC)
Operating temperature
Storage temperature
Humidity
0
o
C to 60
o
C
-40
o
C to 85
o
C
0% to 95% relative humidity, non-condensing
Software
PAC Project Basic
PAC Project Professional
Includes programming, HMI software, and configuration software; included with
purchase of controller.
PAC Project Basic plus OPC 2.0-compliant OPC server, OptoControl strategy and
OptoDisplay project importing, support for serial
mistic
I/O units, and Ethernet link
redundancy support.
Other features
Multiple protocol support including TCP/IP, FTP, SNMP v2.0c (with firmware 8.2a),
Modbus/TCP, EtherNet/IP™, and OptoMMP™.
Real-time clock
FTP server/client with file system (in RAM and in removable storage)
Ethernet link redundancy or network segmenting
Agency certifications
(-W models only) U.S., FCC Part 15 Subpart C; Canada, IC RSS-210
(-FM models only) Factory Mutual approved
* Requires a Wired+Wireless model (SNAP-PAC-S1-W or SNAP-PAC-S2-W)