M4RTU/M4 I/O User’s Guide
93
WORKSHEETS
M4RTU/M4 I/O POWER CONSUMPTION WORKSHEET
Instructions
1.
On the previous worksheet, locate the daughter cards and digital and/or analog modules you will be
using with the M4RTU/M4 I/O. Enter a quantity for each item in the “Quantity” column. Also, fill in the
quantity and wattage of any RS-232 devices on the line provided.
2 . Multiply the value in the “Watts” column by the quantity entered in the “Quantity” column and enter
the result in the “Total” column for each component used.
Example:
Eight G4 digital module totals 0.688 W. Four G4ADX analog modules total 6.4 W.
3.
Add the values in the “Total” column, including the value entered for the M4RTU/M4 I/O base unit,
and enter the result on the “Total Watts” line.
Example:
0.688 W (digital modules) + 6.4 W (analog modules) + 7.5 W (base RTU) = 14.588 W.
4.
Enter the supplied input voltage for your installation on the “Your supplied input voltage” line.
Example:
24 VDC.
5.
Divide the total on the “Total Watts” line by the number entered on the “Your supplied input voltage”
line to calculate your total input current requirements. Enter this number on the last line of the
worksheet.
Example:
14.588 W (total watts)/24 VDC (supplied input) = 0.6 A required input current for the
M4RTU/M4 I/O.
Summary of Contents for Modular M4RTU
Page 6: ...6 M4RTU M4 I O User s Guide TABLE OF CONTENTS...
Page 74: ...74 M4RTU M4 I O User s Guide FIELD WIRING...
Page 80: ...80 M4RTU M4 I O User s Guide PRODUCT SPECIFICATIONS...
Page 82: ...82 M4RTU M4 I O User s Guide ADDRESS JUMPER CONFIGURATION...
Page 86: ...86 M4RTU M4 I O User s Guide UPGRADING RAM AND FLASH EEPROM...
Page 89: ...M4RTU M4 I O User s Guide 89 WORKSHEETS Figure F 3 M4RTUX I O Extender I O Module Worksheet...
Page 91: ...M4RTU M4 I O User s Guide 91 WORKSHEETS Figure F 5 Field Wiring Worksheet Example 2...
Page 94: ...94 M4RTU M4 I O User s Guide WORKSHEETS...