ONICON Incorporated 727-447-6140
Page 9
www.onicon.com
SYSTEM-40 BTU MEASUREMENT SYSTEM
1.7 SERIAL NUMBER
SECTION 2.0
UNPACKING
2.1 CHECKING THAT YOU HAVE
RECEIVED EVERYTHING
1.5 ADDITIONAL HARDWARE
REQUIRED
ONICON’S System-40 is a true heat (BTU) computer, which accepts data from
several sensors, performs a series of computations with that data, and displays
and/or transmits the results as an indication of the amount of heat (BTU) being
transferred per unit time or as a totalized amount.
For direct insertion style meters, a customer supplied line size threaded tee is
required. The kit is ordered with the meter to install the remote temperature
sensor.
For remote style meters, two tees are required. The tees are used with the two ½”
NPT thermowells ordered with the meter. 2½” meters are provided with raised
face flanges. Mating flanges, flange gaskets and mounting hardware are required
to complete the installation.
1.6 WORKING
ENVIRONMENT
The System-40 was designed for installation and use indoors in residential,
commercial and light industrial environments that are free of corrosive liquids
and fumes, temperature extremes and excess vibration. It may be installed
outdoors in protected spaces away from direct sunlight and rain, sleet or snow.
The operating ambient air temperature range is -13°F to 131°F. Electrical power
should be clean, free of excess high frequency noise and large voltage transients.
The serial number is a unique identifier for the product, located on the side of
the enclosure. Please have this number available when contacting ONICON for
assistance.
The System-40 BTU Meter is generally shipped in one package unless optional
hardware or equipment is ordered. Notify the freight carrier and ONICON if any
items are damaged in transit.
The following items are normally provided with the System-40 BTU Meter:
•
Two (2) line size process connection meter couplings with male NPT threads
and sealing gaskets (shipped attached to meter)
•
One (1) line size NPT (or copper sweat) x M10 bushing for the remote
temperature sensor OR two (2) thermowells with ½” male NPT threads
•
One (1) System-40 Installation and Operation Guide
•
One (1) System-40 Certificate of Calibration