SYSTEM-40 BTU MEASUREMENT SYSTEM
4.2.2.3 Auxiliary Input/ Output Configuration Settings
Auxiliary pulsed I/O can be configured after selecting units. The meter can be
programmed at two (2) aux pulsed inputs and one (1) aux pulsed output, OR one
(1) aux pulsed input, one (1) aux pulsed output, and one (1) analog output. The
number of I/O can also be changed through commissioning.
Below is the default setup displays for two (2) aux pulsed inputs and one (1) aux
pulsed output.
One (1) aux pulsed input, one (1) aux pulsed output, and one (1) analog output
set up displays are on the following page.
Aux Config
NEXT
EXIT
EDIT
2 In 1 Out
Num Aux Inputs
NEXT
EXIT
EDIT
2
Aux Input 1
NEXT
EXIT
EDIT
Counts
Aux Input 2
NEXT
EXIT
EDIT
Counts
Pulsed Output 3
NEXT
EXIT
EDIT
Select Type
Set Meter
Press NEXT edit units
of measure
SAVE completes install
with current settings
NEXT
BACK
SAVE
The default auxiliary configuration set as
2 IN 1 OUT
. This can be changed by
select
EDIT
, and then
MORE
. To continue, press
SAVE
, and then
NEXT
.
Press
EDIT
, then
MORE
to select the number of aux input. To continue, press
SAVE
and then
NEXT
.
Press
EDIT
, then
MORE
to define aux input 1. To continue, press
SAVE
and then
NEXT
.
Press
EDIT
, then
MORE
to define aux input 2. To continue, press
SAVE
and then
NEXT
.
Press
EDIT
, then
MORE
to select type of pulse output 3. Options include: Energy
Mode, Volume Mode, Alarm, and Modbus Coil. See 5.3 AUXILIARY OUTPUTS for
more details. To continue, press
SAVE
and then
NEXT
.
Use this menu option to save, exit commissioning and return to normal
operation. Press
NEXT
to repeat the meter set, or press
SAVE
to complete the
installation.
Important Note
Screen may vary based on settings.