Setup and Installation

 

16

ONePlus UPS User Instruction Manual

 

The front panel indicator lights serve four functions: 

1. To indicate status of the UPS, whether operating 

normally or in fault condition. See System Code 
Status Chart on page 27 for details.

2. To indicate % of load connected to the UPS. 

To determine % load, the UPS must be on AC 
power, not on battery. Press and hold the 

 

button until the indication lights illuminate, 
indicating load % as follows: 

 

fig. 7: Percentage of Load or Percentage of Remaining Runtime 
Indicators

 

3. To indicate % of remaining runtime.

To determine % of remaining runtime, the UPS 
must be on battery, not on AC power. Press and 
hold the 

 button until the indication lights 

illuminate. See fig. 7 for determining% of 
remaining runtime.

4. To indicate over temperature. 

When illuminated, the unit has exceeded safe 
operating temperatures. See Table 5, 
“Troubleshooting,” on page 28.

 

Communications

 

With a communications cable and MopUPS

 

®

 

 

Express installed, MopUPS Express can exchange 
data with the UPS. This power management software 
polls the UPS for detailed information on the status 
of the power environment. If a power emergency 
occurs, the software initiates an orderly shutdown of 
the equipment. The interface ports will send On 

100%

75%

50%

25%

Summary of Contents for ONePlus Series

Page 1: ...EAC Virtual Kelvin Ground and MopUPS are all registered trademarks and ONePlus is a trademark of ONEAC Corporation All other trademarks product and corporate names are the property of their respective...

Page 2: ...tion 9 Long Term Storage 9 Ventilation 10 Grounding the Unit 10 Connections 11 ONePlus Front Panel 12 Power Switch 13 Self Test 14 Indicators and Alarms 14 Communications 16 Features and Specification...

Page 3: ...com Technical Support ONEAC offers 24 hour technical support To contact ONEAC Technical Services North America 847 816 6000 option 3 or toll free 800 327 8801 option 3 Europe 44 0 1235 861962 email t...

Page 4: ...ant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when the UPS is operating in a commercial environment The UPS generates uses and can...

Page 5: ...isk of electrical shock Do not use AC adaptors with only two conductors to connect the input line cord to the wall socket as this will not connect the earth ground to the equipment WARNING Dangerous v...

Page 6: ...e Wechselstromadapter mit nur zwei Stromleitern verwenden um das Netzkabel an die Wandsteckdose anzuschlie en weil das Ger t hierdurch nicht an die Erde angeschlossen wird ACHTUNG In diesem Ger t sind...

Page 7: ...Ne pas utiliser d adaptateurs CA n ayant que deux conducteurs pour brancher le cordon d alimentation dans la prise murale car l quipement ne serait pas mis la terre AVERTISSEMENT Cet quipement renferm...

Page 8: ...de descargas el ctricas No utilice adaptadores de CA con s lo dos conductores para conectar el cable de la l nea de entrada al enchufe mural debido a que ste no conectar el equipo a tierra ADVERTENCIA...

Page 9: ...r blackout low voltage and overvoltage events The buck and boost feature will compensate for a wide range of voltage variations without depleting the batteries Battery Backup Mode In an extreme over o...

Page 10: ...aded to more than 105 percent of the UPS rating battery power to the UPS is not available To reset turn the UPS OFF remove some of the load then turn the UPS ON For GS compliance The power distributio...

Page 11: ...rred in transit If damage is evident contact ONEAC Technical Services Installation When selecting a location for your UPS be sure that the unit is near a properly wired AC electrical outlet and is eas...

Page 12: ...at temperatures below 15 C 5 F Ventilation The ventilation requirement for ONePlus is a minimum of 2 inches 50 mm of clearance on all sides Grounding the Unit To eliminate shock hazard connect the un...

Page 13: ...PS Back Panels fig 4 Typical UPS Installation Site Wiring Fault Indicator Serial Communication Port Four 5 15 Receptacles USB Communication Port Input Circuit Breaker Ground Lug USB Communication Port...

Page 14: ...est when it is first plugged in and turned on After the self test the unit enters Normal mode If the alarm sounds or the UPS alarm indicator stays on see Table 4 System Code Status Chart on page 27 NO...

Page 15: ...ds Power is supplied to the output connectors Turn OFF the UPS by pressing the power switch for 2 seconds This turns the power to the output connectors OFF The internal charger will continue to charge...

Page 16: ...here the problem is For more about the LED indicator lights see Troubleshooting on page 28 NOTE Be sure the batteries are fully charged and the UPS is not in Battery mode before initiating the self te...

Page 17: ...s the UPS power switch and hold for 5 seconds remove the load and push the breaker back into its housing Battery Replacement If the UPS has determined that the battery is no longer functional the gree...

Page 18: ...o indicate of remaining runtime To determine of remaining runtime the UPS must be on battery not on AC power Press and hold the button until the indication lights illuminate See fig 7 for determining...

Page 19: ...If a serial connection is required contact the factory to purchase optional serial cable ONEAC part number CA 2B10S 03 NOTE RS232 and USB communications ports cannot be used simultaneously 2 Insert t...

Page 20: ...ct 20 mA 30 VDC contact rating Closes when low Out 2 RxD Receive from external device and shut down input In 3 TxD Transmit to external device Out 4 No connection 5 GND Signal common 6 AC fail AC fail...

Page 21: ...erconnected systems NOTE In order to maintain the full performance benefits of this technology equipment connected to the ONePlus UPS should not externally rebond the grounding connector to building s...

Page 22: ...bjected to 6 kV ANSI IEEE C62 41 Cat A Normal common mode clamping response time Instantaneous Transfer time max 6 milliseconds On battery output voltage Sine wave Buck and Boost maintains output volt...

Page 23: ...age varies between 89 and 152 VAC Nominal Output Voltage on battery 115 VAC On Battery Waveshape sine wave On Battery Frequency 60Hz 1 Transfer Time 6mS max Output Connection 4 5 15R 4 5 15R 6 5 15R 8...

Page 24: ...ity ANSI IEEE C62 41 Category A B 6kV 200 500 Amp 100kHz Ringwave Surge Voltage Let through Less than 10V normal mode L N less than 0 5 V Common mode N G when subjected to ANSI IEEE C62 41 Cat A Norma...

Page 25: ...k Although not necessary AC power can be removed for battery replacement Press the power switch for 2 seconds to turn the unit OFF AND unplug the UPS from the AC power source NOTE The UPS cannot prote...

Page 26: ...the UPS by pulling the top left corner forward and sliding the front panel off see fig 9 fig 9 Removing the Front Panel 2 Remove the metal battery retention plate to access the battery by removing the...

Page 27: ...gulations See Battery Disposal below if you would like ONEAC to dispose of depleted battery Testing New Batteries NOTE Once new batteries are installed it is recommended that the batteries charge 6 24...

Page 28: ...an RMA number Mark the RMA number on the packing slip and shipping carton 2 Phone ONEAC Corporation for the number of a local battery collection site US only 3 Make arrangements with a local auto sho...

Page 29: ...hone or may issue a Return Material Authorization RMA number along with instructions on how to return the UPS if service is required NOTE You will need to supply the service representative with the UP...

Page 30: ...trician Out of frequency range Check for UPS compatibility with power source Site Wiring Fault is ON Ground wire connection does not exist Line and neutral wires are reversed in the line receptacle Co...

Page 31: ...ttery connection or replace battery If green LED is blinking or off the output is overloaded Reduce load on the UPS disconnect one ore more devices and restart the UPS Over Temperature LED is ON UPS i...

Page 32: ...f Warranty This limited warranty does not cover any losses or damage resulting from shipment to or from the customer or from improper installation inappropriate environment abuse modifications adjustm...

Page 33: ...Warranty ONePlus UPS User Instruction Manual 31...

Reviews: