Features and Specifications
ONePlus UPS User Instruction Manual
21
Specifications and Characteristics
Table 2. Physical/Electrical Specifications and Performance Characteristics
Specification and Characteristics
ONePlus250
ONePlus400
ONePlus600
ONePlus1000
Part Number
ONE254AG-SE ONE404AG-SE
ONE604AG-SE
ONE1004AG-SE
Maximum Load VA/W
250/167
400/268
600/402
1000/670
Rated Power Factor
UPS .67
Crest Factor
<3
Nominal Input Voltage
120 VAC
Low Limit for On-line Operation
89 VAC
High Limit for On-line Operation
152 VAC
Frequency Limits (on-line)
60Hz +/ -5%
Input Connection
6’ attached line cord with 5-15P plug
Input Over Current Protection
resettable circuit breaker
Buck and Boost
maintains output voltage between 101 and 132 VAC
while input voltage varies between 89 and 152 VAC
Nominal Output Voltage (on battery)
115 VAC
On Battery Waveshape
sine-wave
On Battery Frequency
60Hz +/- 1%
Transfer Time
6mS, max
Output Connection
(4) 5-15R
(4) 5-15R
(6) 5-15R
(8) 5-20R (T*)
Battery Type
maintenance free, spill proof, sealed lead-acid
Typical Battery Life
2 - 4 years, depends on number of discharges and ambient temperature
Typical Battery Recharge Time
(90% Recovery)
3-6 hours after full discharge to cut off
Communications
isolated basic signaling
Interface Connector
USB and RS232 communications ports
Input Signal - static
inverter shut down [pin 2 (+) to pin 5 (common)]
(+3 to +27 VDC shuts down inverter)
Output Signals - stimulated relay
on battery (pin 9 N.O., (N.C.), pin 5 (common)
Low battery (pin 1 N.O.)
Maximum Collector Voltage
25 VDC
Maximum Collector Current
25 mADC
Operating Temperature**
0 to +40° C (32 to 104° F)
Storage Temperature**
-15 to 45° C (+5 to 113° F)
Relative Humidity
0 to 95%, non-condensing
Table continued on next page.