Setup and Installation
10
ONePlus UPS User Instruction Manual
To keep the battery enclosure fully charged and to
maximize the life of the battery, plug the UPS into an
outlet while it is in storage. If the UPS is stored
without power access, plug it into a power source for
24 hours at least once every 4 - 6 months.
ATTENTION:
If the storage temperature is greater
than 30
°
C (86
°
F) plug the UPS into a power source
for 24 hours every 2 to 3 months.
ATTENTION:
The UPS should not be stored at
temperatures below -15
°
C (+5
°
F).
Ventilation
The ventilation requirement for ONePlus is a
minimum of 2 inches (50 mm) of clearance on all
sides.
Grounding the
Unit
To eliminate shock hazard, connect the unit to a
properly grounded AC receptacle.
Before applying power, verify that the available line
voltage matches the voltage listed on the rear-panel
label.
CAUTION:
Interruption of the protective grounding
conductor or disconnection of the protective earth
terminal presents a potential shock hazard that could
result in personal injury and damage to the
equipment.
NOTE:
When connecting the UPS, make sure that
the receptacle has power available and is not
controlled by a wall switch.