8
1-3 Installing the Controller
Preparation
1-3
Installing the Controller
1-3-1
Installation Precautions
To improve heat radiation, install the Controller only in the orientation show
below.
Important
Install the Controller so that the distance between the Controller and other
devices is at least the dimensions shown in the figure below to improve the
ventilation.
Important
Keep the ambient temperature less than 50 °C. If the ambient temperature is
higher than 50 °C, install a fan forced cooling system or an air conditioner to
keep the temperature lower than 50 °C.
Important
Avoid mounting on a panel, in which high-voltage emitting devices are
installed to prevent ZFX-C operation from being affected by noise.
Important
Allow at least 10 m between the Controller and power lines to keep noise at a
low level in the operating environment.
1-3-2
Installing on the DIN Track
1.
Hook the Controller’s upper hook onto the
DIN track.
2.
Push the Controller down onto the DIN track
until its lower hook is snapped into place.
Important
Attach the End Plate (sold separately) to both sides of the Controller on the
DIN track.
Right
Upward
Wrong
Wrong
Min.
50 mm
Min.
15 mm
When installing Controller only:
When installing the Controller With the Exhaust Unit
attached:
Min.
50 mm
Min. 15 mm
1
2