60
Operating Errors and Countermeasures
Section 5-1
5-1
Operating Errors and Countermeasures
5-1-1
Overview
If an error occurs while the NE1A Logic Simulator is running, a dialog box will
appear with an error message. The errors can be cleared using the following
countermeasures.
5-1-2
File Errors
Error message
Countermeasure
Failed to load EDS
file.
The simulation file that you tried to open is not supported by
the installed Network Configurator. Update the version of the
Network Configurator.
Access to 'file name'
was denied.
1. The simulation file that you tried to save is being used else-
where. Close the application that is using the file.
2. You do not have access rights to the simulation file that you
are trying to open or save. Select a file that you have access
rights to.
A sharing violation
occurred while
accessing 'file
name'.
The simulation file that you tried to open is being used by
another application. Close the application that is using the file.
Processing failed.
1. The file you tried to import is not in timing chart format.
Specify a valid timing chart file.
2. You do not hove access rights to the timing chart file that you
are trying to import or export. Select a file that you have ac-
cess rights to.
The password was
not correct. Please
enter the correct
password.
The entered password does not match the password that has
been set in the logic program. Enter the correct password.
This program is not
complete and can-
not be executed.
Please select an
executable file.
The function block used in the logic program is missing a nec-
essary input. This program cannot be simulated. Correct the
program with the Network Configurator and create the simula-
tion file again.
This program is not
complete and can-
not be download to
the device. Continue
anyway?
The function block used in the logic program is missing an
input or an output. It cannot be downloaded to the actual
device but a simulation can be run.To run a simulation, click
the
YES
Button, otherwise click the
Cancel
Button and correct
the program with the Network Configurator.
The current file will
be overwritten with
'file name' from the
disk. OK?
The file that you tried to open is already open. To overwrite the
already opened file, click the
YES
Button. To leave it and con-
tinue using the already opened file, click the
No
Button.
The file is not valid.
Please specify a
valid file.
1. The file that you tried to import is not in simulation file format.
Specify a valid simulation file.
2. The file that you tried to import is not in timing chart file for-
mat. Specify a valid timing chart file.
Unexpected file for-
mat.
The file that you tried to open or import is not in simulation file
format. Specify a valid simulation file.
Summary of Contents for WS02-CFSC1-E
Page 1: ...OPERATION MANUAL Cat No Z910 E1 02 DeviceNet Safety WS02 CFSC1 E NE1A Logic Simulator...
Page 2: ...DeviceNet Safety WS02 CFSC1 E NE1A Logic Simulator Operation Manual Revised June 2007...
Page 3: ...iv...
Page 9: ...x...
Page 13: ...xiv...
Page 55: ...40 Zooming In and Out of the Logic Window Display Section 3 8...
Page 81: ...66 Shortcut Key List Appendix A...
Page 85: ...70 Revision History...