77
Verifying Data
Section 7-3
The following screen will be displayed if data is not uploaded.
7-3
Verifying Data
Use the following procedure to verify CX-Position data at the computer and
NC Unit data.
1,2,3...
1.
On the project tree, select the NC Unit for verification.
2.
Select Online (L)/Verify (V).
3.
Under Data Type, select the data to be verified. To verify all data, select All
Data. To designate specific data to be verified, select Setting Data, and
then the specific data.
4.
Click the OK Button. (Click the Cancel Button during verification to stop
the verification process.)