CP1E-E
@@
D
@
-
@
CP1E-N
@@
D
@
-
@/
NA20D
@
-
@
10
Item
CP1E-E
@@
D
@
-
@
CP1E-N
@@
D
@
-
@
CP1E-NA
@@
D
@
-
@
Communications
B-type Peripheral USB Port
Conforming to USB 2.0 B type connector
Transmission
distance
5 m max.
Built-in RS-232C port
No built-in RS-232C port
Interface: Conforms to EIA RS-232C.
Communications
method
Half duplex
synchronization
Start-stop
Baud rate
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
Transmission
distance
15 m max.
Supported
protocol
•
Host Link
•
1:N NT Link
•
No-protocol mode
•
Serial PLC Links (master, slave)
•
Modbus-RTU Easy Master
Serial Option port
Option Board cannot be mounted.
1 port (Option Board can be mounted only to N30/40/
60 and NA20 CPU Units.)
Mountable
Option Boards
•
One RS-232C port: CP1W-CIF01
•
One RS-422A/485 port (not isolated): CP1W-CIF11
•
One RS-422A/485 port (isolated): CP1W-CIF12
Communications
method
Depends on Option Board.
synchronization
Depends on Option Board.
Baud rate
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
Compatible
protocols
•
Host Link
•
1:N NT Link
•
No-protocol mode
•
Serial PLC Links (master, slave)
•
Modbus-RTU Easy Master
Number of tasks
17
•
One cyclic execution task
•
One scheduled interrupt task (always interrupt task 1)
•
Six input interrupt tasks (interrupt tasks 2 to 7)
•
Sixteen high-speed counter interrupt tasks (interrupt tasks 1 to 16)
Maximum subroutine number
128
Maximum jump number
128
Scheduled interrupt tasks
1 interrupt task
Clock
Clock function not included.
The time of error occurrence displays 01-01-01
01:01:01 Sunday
Included.
Accuracy (monthly deviation):
-4.5 min to -0.5 min at ambient temperature of 55
o
C,
-2.0 min to +2.0 min at ambient temperature of 25
o
C,
-2.5 min to +1.5 min at ambient temperature of 0
o
C
Memory
backup
Built-in EEPROM
Ladder programs and parameters are automatically saved to built-in EEPROM
A section of the Data Memory Area can be saved to the built-in EEPROM.
Battery backup With
CP1W-BAT01 Battery
(Sold separately)
Battery cannot be mounted.
CP1W-BAT01 can be used.
Maximum battery service life: 5 years
Backup Time
Guaranteed value (ambient temperature: 55
o
C):
13,000 hours (approx. 1.5 years)
Effective value (ambient temperature: 25
o
C):
43,000 hours (approx. 5 years)
CIO Area
Input Bits
1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99)
Output Bits
1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199)
Serial PLC Link Words
1,440 bits (90 words): CIO 200.00 to CIO 289.15 (words CIO 200 to CIO 289)
Work Area (W)
1,600 bits (100 words): W0.00 to W99.15 (W0 to W99)
Holding Area (H)
800 bits (50 words): H0.00 to H49.15 (H0 to H49)
Bits in this area maintain their ON/OFF status when operating mode is changed.
Auxiliary Area (A)
Read-only: 7,168 bits (448 words) A0 to A447
Read/write: 4,896 bits (306 words) in words A448 to A753
Temporary Relay Area (TR) (TR Area)
16 bits: TR0 to TR15
Timer Area (T)
256 timer numbers (T0 to T255 (separate from counters))
Counter Area (C)
256 counter numbers (C0 to C255 (separate from timers))
Data Memory Area (D)
2 Kwords: D0 to D2047
Of these, 1,500 words can be saved to the backup
memory (built-in EEPROM) using settings in the
Auxiliary Area.
8 Kwords: D0 to D8191
Of these, 7,000 words can be saved to the backup
memory (built-in EEP-ROM) using settings in the
Auxiliary Area
Operating modes
PROGRAM mode: Program execution is stopped.
Preparations can be executed prior to program execution in this mode.
MONITOR mode: Programs are executed.
Some operations, such as online editing, and changes to present values in I/O memory, are
enabled in this mode.
RUN mode: Programs are executed.
This is the normal operating mode.
Summary of Contents for SYSMAC CP1E-E10DR-A