CP1E-E
@@
D
@
-
@
CP1E-N
@@
D
@
-
@/
NA20D
@
-
@
18
Allocating Built-in Inputs to Functions
Input terminals are allocated functions by setting parameters in the PLC Setup. Set the PLC Setup so that each terminal is used for only one function.
CPU Unit with
I/O Points
Input terminal block
Settings in PLC Setup
Interrupt input setting on
Built-in Input Tab Page
High-speed counter 0 to 3 setting on
Built-in Input Tab Page
Origin search settings on Pulse
Output 0/1 Tab Page
Terminal
block
label
Terminal
number
Normal
Interrupt
Quick
Single-phase
(increment
pulse input)
Two-phase
(differential
phase x4 or
up/down)
Two-phase
(pulse/
direction)
CPU Unit with
20 to 60 points
CPU Unit with
14 I/O points
Normal
input
Input
interrupt
Quick-
response
input
10
CIO 0
00
Normal
input 0
--
--
Counter 0,
increment input
Counter 0, phase
A or up input
Counter 0,
pulse input
--
--
01
Normal
input 1
--
--
Counter 1,
increment input
Counter 0, phase
B or down input
Counter 1,
pulse input
--
--
02
Normal
input 2
Interrupt
input 2
Quick-response
input 2
Counter 2,
increment input
Counter 1, phase
A or up input
Counter 0,
direction
--
--
03
Normal
input 3
Interrupt
input 3
Quick-response
input 3
--
Counter 1, phase
B or down input
Counter 1,
direction
--
Pulse 0, Origin
proximity input
signal
04
Normal
input 4
Interrupt
input 4
Quick-response
input 4
Counter 3,
increment input
Counter 0, phase
Z or reset input
Counter 0,
reset input
--
--
05
Normal
input 5
Interrupt
input 5
Quick-response
input 5
Counter 4,
increment input
Counter 1, phase
Z or reset input
Counter 1,
reset input
--
Pulse 1, Origin
proximity input
signal
14
06
Normal
input 6
Interrupt
input 6
Quick-response
input 6
Counter 5,
increment input
--
--
Pulse 0: Origin
input signal
Pulse 0, Origin
proximity input
signal
07
Normal
input 7
Interrupt
input 7
Quick-response
input 7
--
--
--
Pulse 1: Origin
input signal
Pulse 1, Origin
proximity input
signal
20
08
Normal
input 8
--
--
--
--
--
--
--
09
Normal
input 9
--
--
--
--
--
--
--
10
Normal
input 10
--
--
--
--
--
Pulse 0: Origin
proximity input signal
--
11
Normal
input 11
--
--
--
--
--
Pulse 1: Origin
proximity input signal
--
30
CIO 1
00 to 05
Normal
input 12
to17
--
--
--
--
--
--
--
40
06 to 11
Normal
input 18
to 23
--
--
--
--
--
--
--
60
CIO 2
00 to 11
Normal
input 24
to 35
--
--
--
--
--
--
--
These functions are supported only by
N/NA-type CPU Units with transistor
outputs.