CP1E-E
@@
D
@
-
@
CP1E-N
@@
D
@
-
@/
NA20D
@
-
@
30
●
Analog I/O Units
●
Temperature Sensors Units
*
Accuracy for a K-type sensor at -100°C or less is ±4°C ±1 digit max.
The rotary switch is used to set the temperature range.
●
CompoBus/S I/O Link Unit
Model
CP1W-MAD11
Item
Voltage I/O
Current I/O
Analog Input
Section
Number of inputs
2 inputs (2 words allocated)
Input signal range
0 to 5 VDC, 1 to 5 VDC,
0 to 10 VDC, or
−
10 to 10 VDC
0 to 20 mA or 4 to 20 mA
Max. rated input
±
15 V
±
30 mA
External input impedance
1 M
Ω
min.
Approx. 250
Ω
Resolution
1/6000 (full scale)
Overall accuracy
25
°
C
0.3% full scale
0.4% full scale
0 to 55
°
C
0.6% full scale
0.8% full scale
A/D conversion data
16-bit binary (4-digit hexadecimal)
Full scale for
−
10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Averaging function
Supported (Settable for individual inputs via DIP switch)
Open-circuit detection function
Supported
Analog Output
Section
Number of outputs
1 output (1 word allocated)
Output signal range
1 to 5 VDC, 0 to 10 VDC, or
−
10 to 10 VDC,
0 to 20 mA or 4 to 20 mA
Allowable external output load resistance
1 k
Ω
min.
600
Ω
max.
External output impedance
0.5
Ω
max.
Resolution
1/6000 (full scale)
Overall accuracy
25
°
C
0.4% full scale
0 to 55
°
C
0.8% full scale
Set data (D/A conversion)
16-bit binary (4-digit hexadecimal)
Full scale for
−
10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Conversion time
2 ms/point (6 ms/all points)
Isolation method
Photocoupler isolation between analog I/O terminals and internal circuits.
No isolation between analog I/O signals.
Current consumption
5 VDC: 83 mA max., 24 VDC: 110 mA max.
Item
CP1W-TS001
CP1W-TS002
CP1W-TS101
CP1W-TS102
Temperature sensors
Thermocouples
Platinum resistance thermometer
Switchable between K and J, but same type must be used for
all inputs.
Switchable between Pt100 and JPt100, but same type must
be used for all inputs.
Number of inputs
2
4
2
4
Allocated input words
2
4
2
4
Accuracy
(The larger of
±
0.5% of converted value or
±
2
°
C)
±
1 digit
max.
*
(The larger of
±
0.5% of converted value or
±
1
°
C)
±
1 digit
max.
Conversion time
250 ms for 2 or 4 input points
Converted temperature data
16-bit binary data (4-digit hexadecimal)
Isolation
Photocouplers between all temperature input signals
Current consumption
5 VDC: 40 mA max., 24 VDC: 59 mA max.
5 VDC: 54 mA max., 24 VDC: 73 mA max.
Setting
CP1W-TS001/TS002
CP1W-TS101/TS102
Input type
Range (
°
C)
Range (
°
F)
Input type
Range (
°
C)
Range (
°
F)
0
K
−
200 to 1,300
−
300 to 2,300
Pt100
−
200.0 to 650.0
−
300.0 to 1,200.0
1
0.0 to 500.0
0.0 to 900.0
JPt100
−
200.0 to 650.0
−
300.0 to 1,200.0
2
J
−
100 to 850
−
100 to 1,500
---
Cannot be set.
3
0.0 to 400.0
0.0 to 750.0
---
4 to F
---
Cannot be set.
---
Model number
CP1W-SRT21
Master/slave
CompoBus/S Slave
Number of I/O points
8 input points, 8 output points
Number of words allocated in CPU
Unit I/O memory
1 input word, 1 output word
Node number setting
Set using the DIP switch
(Set before turning on the CPU Unit’s power supply.)
Summary of Contents for SYSMAC CP1E-E10DR-A