![background image](http://html1.mh-extra.com/html/omron/sysmac-c500/sysmac-c500_installation-manual_743081081.webp)
Specifications
Appendix B
76
Transistor Output Units Continued
3G2A5-OD213
Max. switching
Capacity
16 mA/4.5 V to 100 mA/26.4 VDC (See chart below.) 800 mA/common, 6.4 A/Unit
Leakage Current
0.1 mA max.
Residual Voltage
0.4 V max.
ON Response Time
0.2 ms max.
OFF Response Time
0.3 ms max.
No. of Points
64 (8 points/common, 8 circuits)
Internal Current
Consumption
460 mA 5 VDC max. (140 mA + 5 mA x no. of ON points)
Fuse Capacity
1 per circuit, 8 total (not user replaceable)
Power for External
Supply
170 mA 26.4 VDC max. (2.6 mA x no. of ON points)
Weight
550 grams max.
Summary of Contents for SYSMAC C500
Page 1: ...Cat No W132 E1 4 Programmable Controller SYSMAC C500...
Page 2: ...C500 Programmable Controller Installation Guide Revised May 2000...
Page 37: ...29 SECTION 4 System Connections 4 1 Current Consumption 30 4 2 I O Connections 33...
Page 49: ...43 SECTION 6 Power Considerations...
Page 54: ...49 SECTION 7 Safety Considerations...
Page 58: ...53 A Inspection and Maintenance 54 B Specifications 57 C Standard Models 97 Appendix...
Page 96: ...Appendix B Specifications 91 A shape I O Unit B shape I O Unit...
Page 97: ...Specifications Appendix B 92 C shape I O Unit D shape I O Unit...