Section 2
Description of All Components
13
3G2A5-PS223-E
•
Mounting screw
Do not loosen this screw.
Fuse holder
Contains a MF61NR fuse
(3 A, 250 V, 6.35-dia. x32)
POWER indicator
Lights when power is supplied.
Terminals for
external connections
Mounting screw
Do not loosen this screw.
AC input
Voltage selector
Short: 100 to 120 V
Open: 200 to 240 V
LG
GR
START input
RUN output
Connect a 100 to 120 VAC or 200
to 240 VAC power source.
Short these terminals to select 100
to 120 VAC. Open them to select
200 to 240 VAC.
Ground this terminal at a resis-
tance of less than 100
Ω
to im-
prove noise immunity or prevent
electric shock.
Ground this terminal at a resis-
tance of less than 100
Ω
to pre-
vent electric shock.
24 VDC output terminals are not
provided.
These terminals are short-circuited
as a factory-set condition. Remove
the short-circuit bracket to start or
stop the PC with an external signal.
Normally, leave them short-
circuited.
These terminals are turned ON
during RUN operation.
3G2A5-PS213-E
-
+
•
Mounting screw
Do not loosen this screw.
Fuse holder
Contains a MF61NR fuse
(3 A, 250 V, 6.35-dia. x32)
POWER indicator
Lights when power is supplied.
Terminals for
external connections
Mounting screw
Do not loosen this screw.
24 VDC input
LG
GR
START input
RUN output
Connect a 24 VDC power source
(2.3 A min.)
Ground this terminal at a resistance
of less than 100
Ω
to improve noise
immunity or prevent electric shock.
Ground this terminal at a resistance
of less than 100
Ω
to prevent elec-
tric shock.
24 VDC output terminals are not
provided.
These terminals are short-circuited
as a factory-set condition. Remove
the short-circuit bracket to start or
stop the PC with an external signal.
Normally, leave them short-
circuited.
These terminals are turned ON dur-
ing RUN operation.
Summary of Contents for SYSMAC C500
Page 1: ...Cat No W132 E1 4 Programmable Controller SYSMAC C500...
Page 2: ...C500 Programmable Controller Installation Guide Revised May 2000...
Page 37: ...29 SECTION 4 System Connections 4 1 Current Consumption 30 4 2 I O Connections 33...
Page 49: ...43 SECTION 6 Power Considerations...
Page 54: ...49 SECTION 7 Safety Considerations...
Page 58: ...53 A Inspection and Maintenance 54 B Specifications 57 C Standard Models 97 Appendix...
Page 96: ...Appendix B Specifications 91 A shape I O Unit B shape I O Unit...
Page 97: ...Specifications Appendix B 92 C shape I O Unit D shape I O Unit...