![background image](http://html1.mh-extra.com/html/omron/sysmac-c500/sysmac-c500_installation-manual_743081076.webp)
Specifications
Appendix B
71
Triac Output Units
3G2A5-OA121
3G2A5-OA222
Max. switching
Capacity
1 A 132 VAC, 50/60 Hz (4 A/common, 5 A/Unit)
1 A 250 VAC, 50/60 Hz (4 A/common, 5 A/Unit)
Min. switching
Capacity
10 mA (resistive load)
40 mA (inductive load) 10 VAC
10 mA (resistive load)
40 mA (inductive load) 10 VAC
Leakage Current
3 mA (100 VAC) max.
3 mA (100 VAC) max., 6 mA (200 VAC) max.
Residual Voltage
1.2 V max.
1.2 V max.
ON Response Time
1 ms max.
1 ms max.
OFF Response Time
1/2 of load frequency max.
1/2 of load frequency max.
No. of Points
16 (8 points/common, 2 circuits)
16 (8 points/common, 2 circuits)
Internal Current
Consumption
300 mA 5 VDC max.
300 mA 5 VDC max.
Fuse Capacity
5 A 250 V (two fuses)
5 A 250 V (two fuses)
Weight
500 grams max.
500 grams max.
Circuit
Configuration
Inter-
nal
Circuit
OUT 00
OUT 07
COM
OUT 08
OUT 15
to
to
COM
Fuse/fuse blowout
detection circuit
22
Ω
0.022
µ
F
Fuse/fuse blowout
detection circuit
22
Ω
0.022
µ
F
OUT 06
OUT 14
The fuse used in this diagram is 5 A 250 V
6.35 dia. x 32.
Inter-
nal
Circuit
OUT 00
OUT 07
COM
OUT 08
OUT 15
to
to
COM
Fuse/fuse blowout
detection circuit
22
Ω
0.022
µ
F
Fuse/fuse blowout
detection circuit
22
Ω
0.022
µ
F
OUT 06
OUT 14
The fuse used in this diagram is 5 A 250 V
6.35 dia. x 32.
Terminal
Connections
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
2
3
4
5
COM
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
0
1
6
7
8
9
10
11
12
13
14
15
COM
~
~
19
NC
NC
132 VAC max.
132 VAC max.
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
2
3
4
5
COM
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
0
1
6
7
8
9
10
11
12
13
14
15
COM
~
~
19
NC
NC
250 VAC max.
250 VAC max.
Dimensions
A-shape
A-shape
Summary of Contents for SYSMAC C500
Page 1: ...Cat No W132 E1 4 Programmable Controller SYSMAC C500...
Page 2: ...C500 Programmable Controller Installation Guide Revised May 2000...
Page 37: ...29 SECTION 4 System Connections 4 1 Current Consumption 30 4 2 I O Connections 33...
Page 49: ...43 SECTION 6 Power Considerations...
Page 54: ...49 SECTION 7 Safety Considerations...
Page 58: ...53 A Inspection and Maintenance 54 B Specifications 57 C Standard Models 97 Appendix...
Page 96: ...Appendix B Specifications 91 A shape I O Unit B shape I O Unit...
Page 97: ...Specifications Appendix B 92 C shape I O Unit D shape I O Unit...