Section 4
System Connections
32
Special I/O Units
Unit
Model
Current
Consumption (A)
A/D Converter Input
3G2A5-AD001 to- AD005
0.3 each
3G2A5-AD006
0.75 each
3G2A5-AD007
C500-AD101
0.88
C500-AD501
1.2
D/A Converter Output
3G2A5-DA001 to -DA005
0.55 each
C500-DA101
1.3
High-speed Counter
3G2A5-CT001
0.3
g
3G2A5-CT012
0.55
C500-CT041
1.0
Magnetic Card Reader
3G2A5-MGC01
1.0
PID
3G2A5-PID01-E
1.4
Position Control
3G2A5-NC103-E
Total 1.4
3G2A5-TU001-E
3G2A5-NC111-EV1
Total 1.0
3G2A5-TU001-E
3G2A5-NC221-E
Total 1.3
3G2A5-TU001
ASCII
C500-ASC04
0.5 each
ID Sensor
C500-IDS01-V2/IDS02-V1
0.4 each
C500-IDS21/IDS22
Ladder Program I/O
3G2A5-LDP01-V1
0.8
File Memory
C1000H-FMR11
0.35 each
y
C1000H-FMR21
Cam Positioner
C500-CP131
0.35
Link Units and Remote
I/O Units
Unit
Model
Current
Consumption (A)
I/O Link
3G2A5-LK010-(P)E
0.6
PC Link
C500-LK009-V1
0.9
Host Link
C500-LK103 (-P)
1.0 each
C500-LK203
Optical Remote I/O Master
3G2A5-RM001-(P)EV1
0.7
SYSMAC Net Link
C500-SNT31-V4
1.4
Wired Remote I/O Master
C500-RM201
0.3
Summary of Contents for SYSMAC C500
Page 1: ...Cat No W132 E1 4 Programmable Controller SYSMAC C500...
Page 2: ...C500 Programmable Controller Installation Guide Revised May 2000...
Page 37: ...29 SECTION 4 System Connections 4 1 Current Consumption 30 4 2 I O Connections 33...
Page 49: ...43 SECTION 6 Power Considerations...
Page 54: ...49 SECTION 7 Safety Considerations...
Page 58: ...53 A Inspection and Maintenance 54 B Specifications 57 C Standard Models 97 Appendix...
Page 96: ...Appendix B Specifications 91 A shape I O Unit B shape I O Unit...
Page 97: ...Specifications Appendix B 92 C shape I O Unit D shape I O Unit...