Section 6
Power Considerations
46
DC Connections
Screw (4 mm head with
selfraising pressure plate)
z
Power line
•
Use AWG 14 twisted-pair
cable (cross-sectional area: 2
mm
2
min.)
•
Supply 24 VDC
•
Keep voltage fluctuations
within the specified range
(refer to
Appendix B Specifi-
cations)
Screw (4 mm head with
selfraising pressure plate)
3G2A5-PS212-E
3G2A5-PS213-E
-
+
-
+
Breaker
8.6 mm max.
8.6 mm max.
Be sure to use a wire of at least 1.25 mm
2
in thickness.
Use M4 screws for tightening crimp terminals. Use crimp terminals
for wiring. Do not connect bare stranded wires directly to terminal
blocks.
Tighten the terminal block screws to a torque of 1.2 N
S
m.