2-7
Section
Error Processing
34
Note
Disconnection detection (82) operates for input numbers used with a range of 1
to 5 V (4 to 20 mA).
Errors indicated with 8
j
codes are automatically reset when proper counter-
measures are taken. The errors indicated with F
j
codes are cleared when the
power is turned on after making the correct settings and when the Special I/O
Unit Restart Bit is turned OFF, ON, and OFF again.
2-7-3 Errors Detected by CPU Unit
When the CPU Unit detects an error at a Special I/O Unit, it outputs to the CPU
Unit’s SR and AR areas as shown below.
Special I/O Unit Error Flag
Bit
Error
Contents
CPU Unit status
LED indicators
25415
I/O UNIT OVER
The same unit number
has been set for more
than one Special I/O Unit.
CPU Unit operation is
stopped.
RUN:
Not lit
ERROR: Not lit
SPECIAL I/O UNIT
ERROR
Error occurred in I/O
refresh between Special
I/O Unit and CPU Unit.
Operation is stopped only
for faulty Unit.
RUN:
Not lit
ERROR: Not lit
Special I/O Unit Error Flags
Bits
Functions
C200HX/HG/HE
C200H/HS
28200
AR 0000
Unit #0 Error Flag
Turns ON for any unit
b
h
I/O
28201
AR 0001
Unit #1 Error Flag
y
number when I/O
UNIT OVER or
28202
AR 0002
Unit #2 Error Flag
UNIT OVER or
SPECIAL I/O UNIT
28203
AR 0003
Unit #3 Error Flag
SPECIAL I/O UNIT
ERROR occurs.
28204
AR 0004
Unit #4 Error Flag
28205
AR 0005
Unit #5 Error Flag
28206
AR 0006
Unit #6 Error Flag
28207
AR 0007
Unit #7 Error Flag
28208
AR 0008
Unit #8 Error Flag
28209
AR 0009
Unit #9 Error Flag
28210 (See note.)
---
Unit #A Error Flag
28211 (See note.)
---
Unit #B Error Flag
28212 (See note.)
---
Unit #C Error Flag
28213 (See note.)
---
Unit #D Error Flag
28214 (See note.)
---
Unit #E Error Flag
28215 (See note.)
---
Unit #F Error Flag
Note
SR bits 28210 to 28215 cannot be used with C200HE and C200HX/HG-
CPU3
j
-E/4
j
-E PCs.
2-7-4 Restarting Special I/O Units
There are two ways to restart Special I/O Unit operation after having changed
DM contents or having corrected the cause of an error. The first way is to power
up the PC again, and the second way is to turn the Special I/O Unit Restart Bit
ON and then OFF again.