2-1
Section
Specifications
10
2-1
Specifications
2-1-1 General Specifications
All general specifications of the C200H-AD003 Analog Input Unit conform to
those of the C200H, C200HS, and C200HX/HG/HE Series.
2-1-2 Performance Specifications
Item
C200H-AD003
Voltage input
Current input
Number of analog inputs
8
Input signal range (note 1)
0 to 10 V
–10 to 10 V
1 to 5 V
4 to 20 mA
Max. input signal (note 2)
±
15 V
±
30 mA
Input impedance
1 M
Ω
min.
250
Ω
(rated value)
Resolution
1/4000 (full scale)
Converted output data
16-bit binary data
Accuracy
(note 3)
23
°
±
2
°
C
±
0.2% of full scale
±
0.4% of full scale
(note 3)
0
°
to 55
°
C
±
0.4% of full scale
±
0.6% of full scale
Conversion time (note 4)
1.0 ms/point
Isolation
Between input terminals and PC: photocoupler
(No isolation between individual input signals.)
External connectors
28-point terminal block (M3 screws)
Power consumption
100 mA max. at 5 VDC
100 mA max. at 26 VDC
Dimensions
34.5 x 130 x 128 (W x H x D) mm (refer to
Appendix A
Dimensions
)
Weight
450 g max.
Note
1. The input signal range can be set individually for each input.
2. Operation in ranges beyond the maximum input signals will damage the
Unit. Operate within the ranges listed above.
3. The accuracy is given for full scale. For example, an accuracy of
±
0.2%
means a maximum error of
±
8 (BCD).
The default setting is adjusted with the voltage input. When using the current
input, perform the offset and gain adjustment as required.
4. A/D conversion time is the time it takes for an analog signal to be stored in
memory as converted data after it has been input. It takes at least one cycle
before the converted data is read by the CPU Unit.
By executing an I/O refresh, the conversion time may be extended by an
additional 0.3 ms approximately.