3-2
Section
Nomenclature and Functions
41
Check to be sure that the black terminal block mounting screw is securely tight-
ened to a torque of 0.5 N
S
m.
Fasten the mounting screw.
3-2-1 Indicators
The RUN and ERROR indicators show the operating status of the Unit. The fol-
lowing table shows the meanings of the indicators.
LED
Indicator
Operating status
RUN (green)
Lit
Operating in normal mode.
(g
)
Flashes
Operating in adjustment mode.
Not lit
Abnormal (Unit operation stopped)
ERROR (red)
Lit
Error occurred. The error codes are stored in bits
08 to 15 of word n+9.
Not lit
Other than the above.
3-2-2 Unit Number Switch
The CPU Unit and Analog Output Unit exchange data via the IR area and the DM
area. The IR and DM word addresses that each Analog Input Unit occupies are
set by the unit number switch on the front panel of the Unit.
Always turn off the power before setting the unit number. Use a flat-blade screw-
driver, being careful not to damage the slot in the screw. Be sure not to leave the
switch midway between settings.
Switch setting
Unit number
IR words
DM words
0
Unit #0
IR 100 to 109
DM 1000 to 1099
1
Unit #1
IR 110 to 119
DM 1100 to 1199
2
Unit #2
IR 120 to 129
DM 1200 to 1299
3
Unit #3
IR 130 to 139
DM 1300 to 1399
4
Unit #4
IR 140 to 149
DM 1400 to 1499
5
Unit #5
IR 150 to 159
DM 1500 to 1599
6
Unit #6
IR 160 to 169
DM 1600 to 1699
7
Unit #7
IR 170 to 179
DM 1700 to 1799
8
Unit #8
IR 180 to 189
DM 1800 to 1899
9
Unit #9
IR 190 to 199
DM 1900 to 1999
A
Unit #A
IR 400 to 409
DM 2000 to 2099
B
Unit #B
IR 410 to 419
DM 2100 to 2199
C
Unit #C
IR 420 to 429
DM 2200 to 2299
D
Unit #D
IR 430 to 439
DM 2300 to 2399
E
Unit #E
IR 440 to 449
DM 2400 to 2499
F
Unit #F
IR 450 to 459
DM 2500 to 2599
Note
1. Switches A to F can be set for the C200HX/HG-CPU5
j
-E/6
j
-E. Setting
numbers A to F for C200H, C200HS, C200HE, or C200HX/HG-
CPU3
j
-E/4
j
-E PCs will cause an I/O UNIT OVER error and the Unit will
not operate.