4-1
Section
Specifications
66
4-1
Specifications
4-1-1 General Specifications
All general specifications of the C200H-MAD01 Analog I/O Unit conform to
those of the C200H, C200HS, and C200HX/HG/HE Series.
4-1-2 Performance Specifications
Item
C200H-MAD01
Voltage I/O
Current I/O
Input
Number of analog inputs
2
p
Input signal range (note
1)
0 to 10 V
–10 to 10 V
1 to 5 V
4 to 20 mA
Max. input signal (note 2)
±
15 V
±
30 mA
Input impedance
1 M
Ω
min.
250
Ω
(rated value)
Resolution
1/4000 (full scale)
Converted output data
16-bit binary data
Accuracy
(note 3)
23
°
±
2
°
C
±
0.2% of full scale
±
0.4% of full scale
(note 3)
0
°
to
55
°
C
±
0.4% of full scale
±
0.6% of full scale
Output
Number of analog outputs 2
p
Output signal range (note
1)
0 to 10 V
–10 to 10 V
1 to 5 V
4 to 20 mA
Output impedance
0.5
Ω
max.
---
Max. output current
12 mA
---
Max. load resistance
---
600
Ω
max. (note 5)
Resolution
1/4000 (full scale)
Set data
16-bit binary data
Accuracy
(note 3)
23
°
±
2
°
C
±
0.3% of full scale
±
0.5% of full scale
(note 3)
0
°
to
55
°
C
±
0.5% of full scale
±
0.8% of full scale
Com-
Conversion time (note 4)
1.0 ms/point max.
mon
Isolation
Between I/O terminals and PC: photocoupler
(No isolation between individual input and
output signals.)
External connectors
28-point terminal block (M3 screws)
Power consumption
100 mA max. at 5 VDC
200 mA max. at 26 VDC
Dimensions
34.5 x 130 x 128 (W x H x D) mm (refer to
Appendix A Dimensions
)
Weight
450 g max.
Note
1. The I/O signal range can be set individually for each input.
2. Operate within the ranges listed above. Operation in ranges beyond the
maximum input signals will damage the Unit.
3. The accuracy is given for full scale. For example, an accuracy of
±
0.2%
means a maximum error of
±
8 (BCD).
The default setting is adjusted with the voltage input for the analog input and
with the current output for the analog output. When using the current input
and voltage output, perform the offset and gain adjustment as required.