S8VS
Note:
Refer to page 5 for notes 1 to 11.
Power ratings
120 W
180 W
Type
Item
Standard
Maintenance
forecast monitor
Total run time
monitor
Standard
Maintenance
forecast monitor
Total run time
monitor
Efficiency (typical)
80% min.
Input
Voltage (See note 1.)
100 to 240 VAC (85 to 264 VAC)
Frequency (See note 1.)
50/60 Hz (47 to 63 Hz)
Current
100-V input
1.9 A max.
2.9 A max.
200-V input
1.1 A max.
1.6 A max.
Power factor
0.95 min.
Harmonic current emissions
Conforms to EN61000-3-2
Leakage current
100-V input
0.5 mA max.
200-V input
1.0 mA max.
Inrush current
(See note 2.)
100-V input
25 A max. (for a cold start at 25°C)
200-V input
50 A max. (for a cold start at 25°C)
Output
Voltage adjustment range
(See note 3.)
−
10% to 15% (with V.ADJ) (guaranteed)
Ripple
2.0% (p-p) max. (at rated input/output voltage)
Input variation influence
0.5% max. (at 85 to 264 VAC input, 100% load)
Load variation influence
(rated input voltage)
1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence
0.05%/°C max.
Startup time (See note 2.)
1,000 ms max. (at rated input/output voltage)
Hold time (See note 2.)
20 ms min. (at rated input/output voltage)
Addition-
al func-
tions
Overload protection (See note 2.)
105% to 160% of rated load current, voltage drop, intermittent, automatic reset
Overvoltage protection
(See notes 2 and 4.)
Yes
Output voltage indication (See note 5.)
No
Yes (selectable) (See note 6.)
No
Yes (selectable) (See note 6.)
Output current indication (See note 5.)
No
Yes (selectable) (See note 7.)
No
Yes (selectable) (See note 7.)
Peak-hold current indication
(See note 5.)
No
Yes (selectable) (See note 8.)
No
Yes (selectable) (See note 8.)
Maintenance forecast monitor indica-
tion (See note 5.)
No
Yes (selectable)
No
No
Yes (selectable)
No
Maintenance forecast monitor output
No
Yes (transistor out-
put), 30 VDC max.,
50 mA max.
(See note 9.)
No
No
Yes (transistor out-
put), 30 VDC max.,
50 mA max.
(See note 9.)
No
Total run time monitor indication
(See note 5.)
No
Yes
(selectable)
No
Yes
(selectable)
Total run time monitor output
(See note 5.)
No
Yes (transistor out-
put), 30 VDC max.,
50 mA max.
(See note 9.)
No
Yes (transistor out-
put), 30 VDC max.,
50 mA max.
(See note 9.)
Undervoltage alarm indication
(See note 5.)
No
Yes (selectable)
No
Yes (selectable)
Undervoltage alarm output terminals
No
Yes (transistor output), 30 VDC max., 50 mA
max.
(See note 9.)
No
Yes (transistor output), 30 VDC max., 50 mA
max.
(See note 9.)
Parallel operation
No
Series operation
Yes for up to 2 Power Supplies (with external diode)
Other
Operating ambient temperature
Refer to the derating curve in
Engineering Data (60-W, 90-W, 120-W, 180-W, 240-W, and 480-W Models)
. (with no icing or condensation)
Storage temperature
−
25 to 65°C
Operating ambient humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA)
Insulation resistance
100 M
Ω
min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions
Shock resistance
150 m/s
2
, 3 times each in ±X, ±Y, and ±Z directions
Output indicator
Yes (color: green)
EMI
Conducted
Emissions
Conforms to EN61204-3 EN55011 Class A and based on FCC Class A
Conforms to EN61204-3 EN55011 Class B (See note 10.)
Radiated
Emissions
Conforms to EN61204-3 EN55011 Class A
Conforms to EN61204-3 EN55011 Class B (See note 10.)
EMS
Conforms to EN61204-3 high severity levels
Approved standards
UL: UL508 (Listing), UL60950-1
cUL: CSA C22.2 No.14, No.60950-1
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805 Teil 1)
SELV (EN60950/UL50178/UL60950-1)
According to VDE0106/P100, IP20
SEMI
F47-0200 (200-VAC input)
Weight
550 g max.
850 g max.
http://www.ia.omron.com/
6
(c)Copyright OMRON Corporation 2007 All Rights Reserved.