S8VS

Note: 1.

Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal 
temperature of the Power Supply may result in ignition or burning.

2.

Refer to 

Engineering Data (60-W, 90-W, 120-W, 180-W, 240-W, and 480-W Models)

 on page 21 for details.

3.

If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more 
than +10% for 240-W models). When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure 
that the load is not damaged. 

4.

To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.

5.

Displayed on 7-segment LED. (character height: 8 mm)

6.

Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: 

±

2% (percentage of output voltage value, 

±

1 digit)

7.

Resolution of output current indication: 0.1 A; Precision of output current indication: 

±

5% F.S. 

±

1 digit max. (specified by rated output 

voltage)

8.

Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: 

±

5% F.S. 

±

1 digit max. (specified by rated 

output voltage);
Signal width required for peak-hold current: 20 ms

9.

A Type and B Type: Sinking, AP Type and P Type: Sourcing

10.

To ensure the emission rating, a ferrite ring core should be used in all cabling (TDK HF60T, HF70RH or equivalent model).

11.

To ensure the emission rating, a ferrite ring core should be used in all cabling (SEIWA E04SR301334 or equivalent model).

Power ratings

60 W

90 W

Type

Item

Standard

Maintenance 

forecast monitor

Total run time 

monitor

Standard

Maintenance forecast 

monitor

Total run time monitor

Efficiency (typical)

78% min.

80% min.

Input

Voltage (See note 1.)

100 to 240 VAC (85 to 264 VAC)

Frequency (See note 1.)

50/60 Hz (47 to 450 Hz)

Current

100-V input

1.7 A max.

2.3 A max.

200-V input

1.0 A max.

1.4 A max.

Power factor

---

Harmonic current emissions

Conforms to EN61000-3-2

Leakage current

100-V input

0.5 mA max.

200-V input

1.0 mA max.

Inrush current 
(See note 2.)

100-V input

25 A max. (for a cold start at 25°C)

200-V input

50 A max. (for a cold start at 25°C)

Output

Voltage adjustment range 
(See note 3.)

10% to 15% (with V. ADJ)

Ripple

2.0% (p-p) max. (at rated input/output voltage)

Input variation influence

0.5% max. (at 85 to 264 VAC input, 100% load)

Load variation influence 
(rated input voltage)

1.5% max. (with rated input, 0 to 100% load)

Temperature variation influence

0.05%/°C max.

Startup time (See note 2.)

1,000 ms max. (at rated input/output voltage)

Hold time (See note 2.)

20 ms min. (at rated input/output voltage)

Additional 
functions

Overload protection (See note 2.)

105% to 160% of rated load current, voltage drop, intermittent, automatic reset

Overvoltage protection 
(See notes 2 and 4.)

Yes

Output voltage indication (See note 5.)

No

Yes (selectable) (See note 6.)

No

Yes (selectable) (See note 6.)

Output current indication (See note 5.)

No

Yes (selectable) (See note 7.)

No

Yes (selectable) (See note 7.)

Peak-hold current indication 
(See note 5.)

No

Yes (selectable) (See note 8.)

No

Yes (selectable) (See note 8.)

Maintenance forecast monitor indica-
tion (See note 5.)

No

Yes (selectable)

No

No

Yes 
(selectable)

No

Maintenance forecast monitor output 

No

Yes (transistor output), 30 
VDC max., 50 mA max. 
(See note 9.)

No

Total run time monitor indication 
(See note 5.)

No

Yes 
(selectable)

No

Yes 
(selectable)

Total run time monitor output 
(See note 5.)

No

Yes 
(transistor output), 30 
VDC max., 50 mA max. 
(See note 9.)

Undervoltage alarm indication 
(See note 5.)

No

Yes (selectable)

No

Yes (selectable)

Undervoltage alarm output terminals

No

Yes (transistor output) 
30 VDC max., 50 mA max. (See note 9.)

Parallel operation

No

Series operation

Yes for up to 2 Power Supplies (with external diode)

Other

Operating ambient temperature

Refer to the derating curve in 

Engineering Data (60-W, 90-W, 120-W, 180-W, 240-W, and 480-W Models)

. (with no icing or condensation)

Storage temperature

25 to 65°C

Operating ambient humidity

25% to 85% (Storage humidity: 25% to 90%)

Dielectric strength

3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA) 
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current: 20 mA)
500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA) 

Insulation resistance

100 M

Ω

 min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC

Vibration resistance

10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions

Shock resistance

150 m/s

2

, 3 times each in ±X, ±Y, and ±Z directions

Output indicator

Yes (color: green)

EMI

Conducted 
Emissions

Conforms to EN61204-3 EN55011 Class A and based on FCC Class A
Conforms to EN61204-3 EN55011 Class B (See note 10.)

Radiated 
Emissions

Conforms to EN61204-3 EN55011 Class A
Conforms to EN61204-3 EN55011 Class B (See note 10.)

EMS

Conforms to EN61204-3 high severity levels

Approved standards

UL: UL508 (Listing; Class 2: Per UL1310), UL60950-1
cUL: CSA C22.2 No.14 (Class 2), No.60950-1 
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805 Teil 1)
SELV (EN60950/EN50178/UL60950-1)
According to VDE0106/P100, IP20

UL: UL508 (Listing), UL60950-1
cUL: CSA C22.2 No.14, No.60950-1
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805 Teil 1)
SELV (EN60950/EN50178/UL60950-1)
According to VDE0106/P100, IP20

SEMI

F47-0200 (200-VAC input)

Weight

330 g max.

490 g max.

http://www.ia.omron.com/

5

(c)Copyright OMRON Corporation 2007   All Rights Reserved. 

Summary of Contents for S8VS Series

Page 1: ...05 Teil 1 15 30 W Models Compact Thin Power Supplies That Mount Just About Anywhere to Contribute to Control Panel Downsizing Compact thin size 22 5 85 96 5 mm W H D Three mounting directions standard...

Page 2: ...0 W models 1 2 3 4 S8VS 1 Power Ratings 015 15 W 030 30 W 060 60 W 090 90 W 120 120 W 180 180 W 240 240 W 480 480 W 2 Output voltage 05 5 V 12 12 V 24 24 V 3 Indication monitor None Without indication...

Page 3: ...0 A Peak current 30 A 200 VAC S8VS 48024 Power ratings Input voltage Output voltage Output current Alarm output Model number 60 W 100 to 240 VAC 24 V 2 5 A S8VS 06024A 90 W 3 75 A Sinking S8VS 09024A...

Page 4: ...in at rated input output voltage Additional functions Overload protection See note 2 105 to 160 of rated load current voltage drop automatic reset 105 to 160 of rated load current voltage drop intermi...

Page 5: ...ted load current voltage drop intermittent automatic reset Overvoltage protection See notes 2 and 4 Yes Output voltage indication See note 5 No Yes selectable See note 6 No Yes selectable See note 6 O...

Page 6: ...le Total run time monitor output See note 5 No Yes transistor out put 30 VDC max 50 mA max See note 9 No Yes transistor out put 30 VDC max 50 mA max See note 9 Undervoltage alarm indication See note 5...

Page 7: ...age alarm output terminals No Yes transistor output 30 VDC max 50 mA max See note 9 No Yes transistor output 30 VDC max 50 mA max See note 9 Parallel operation No Series operation Yes for up to 2 Powe...

Page 8: ...r smoothing circuit Noise filter AC L INPUT AC N Drive control circuit DC OUTPUT Fuse 3 15 A Overcurrent circuit Current detection circuit Arithmetic operation circuit Display circuit Switch Overvolta...

Page 9: ...S 18024BP Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit Rectifier smoothing circuit Arithmet...

Page 10: ...oothing circuit Rectifier smoothing circuit Photocoupler Display circuit Switch Harmonic current suppression Smoothing Inrush current protection circuit Voltage detection circuit Overvoltage detection...

Page 11: ...ways ground this terminal No Name Function 1 AC Input terminals L N Connect the input lines to these terminals See note 1 2 Protective Earth terminal PE Connect the ground line to this terminal See no...

Page 12: ...d output voltage To reset the power supply leave the power supply off for more than 3 minutes and then turn it on again Note 1 Do not turn ON the power again until the cause of the overvoltage has bee...

Page 13: ...a direct current DC output is ON 5 Output voltage adjuster V ADJ Use to adjust the voltage 6 Main display Red See note 3 Indicates the measurement or set value 7 Operation indicator Orange See note 3...

Page 14: ...ecast monitor Blinks during setup of maintenance forecast monitor setting S8VS 48024A kh Lights up during indication of total run time monitor Blinks during setup of total run time monitor S8VS 48024B...

Page 15: ...ting mode Press and hold Up key U or Down Key D for three seconds or more Output voltage Voltage output by Power Supply is monitored and displayed Output current Current output by Power Supply is moni...

Page 16: ...indicated Press Key output load indication When the maintenance forecast monitor or overheat alarm is indicated Press Key undervoltage alarm indication 2 The above displays are for models with a main...

Page 17: ...atic reset No change e01 Undervoltage alarm set value memory error Undervoltage output terminal DC LOW turns OFF Press and hold the Up Key U 9 or Down Key D 10 for three seconds and check the set valu...

Page 18: ...etting is less than 2 0 years the indication changes to a value 1 5 after the remaining time becomes less than two years and after the remaining time becomes less than the set time an alarm a02 and th...

Page 19: ...nance forecast monitor are not issued 2 The maintenance forecast is accelerated or decelerated according to operating conditions Periodically check indication 3 Acceleration or deceleration of the mai...

Page 20: ...lue reached OFF i e no continuity at the total run time output terminal kh The alarm set value can be changed in the setting mode Example Alarm Displays When a Total Run Time Set Value of 88 kh Is Rea...

Page 21: ...8VS 48024 only The peak current must satisfy the following conditions Input voltage range 200 to 240 VAC Peak current value 30 A max Peak current pulse width 2 s max Cycle 60 s min Note 1 Two seconds...

Page 22: ...ince the AC power is supplied 2 The alarm is not indicated in the setting mode 3 Press the Mode Key 8 after the output voltage is restored to reset alarm indication 4 The undervoltage alarm function m...

Page 23: ...15 W S8VS 030 30 W 97 11 3 35 4 108 3 1 40 10 74 95 Five M4 with square washer Rail stopper 4 5 Sliding 15 max S8VS 06024 60 W S8VS 06024 60 W 110 5 10 8 34 9 121 3 1 94 115 10 50 Five M4 with square...

Page 24: ...M4 with square washer Rail stopper 4 5 Sliding 15 max Rail stopper Screwless block 2 5 mm pitches S8VS 24024 240 W S8VS 24024 240 W S8VS 48024 480 W S8VS 48024 480 W 10 70 Rail stopper Nine M4 with sq...

Page 25: ...els S82Y VS10S Side mounting Bracket For 180 W models S82Y VS15S Side mounting Bracket For 240 W models S82Y VS20S Front mounting Bracket For 60 90 120 180 and 240 W models S82Y VS10F 7 1 3 5 0 5 15 1...

Page 26: ...W 120 W 180 W 240 W and 480 W Models Note The rated current for output terminals is 10 A per terminal Be sure to use multiple terminals simultaneously for current that exceeds the terminal rating Inst...

Page 27: ...e main display 6 changes to a02 An inactive output Yrs kh no continuity in the a02 indication indicates the correct function 4 Release keys to return to the regular state Note DC output stays ON durin...

Page 28: ...n series the current flowing through the load must not exceed the smaller rated output current 3 Serial operation is not possible with 5 V and 12 V models Parallel Operation The Product is not designe...

Page 29: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syst...

Reviews: