S8VS

Ambient Operating and Storage 
Environments 

Store the Power Supply at a temperature of 

25 to 65°C and a 

humidity of 

25% to 90%.

Do not use the Power Supply in areas outside the derating curve 
otherwise, internal parts may occasionally deteriorate or be 
damaged.

Use the Power Supply at a humidity of 25% to 85%.

Do not use the Power Supply in locations subject to direct sunlight.

Do not use locations where liquids, foreign matter, or corrosive gases 
may enter the interior of Products.

S8VS-

@@@

24A

@

 Models only

Satisfy the following conditions when storing the Power Supply for 
long periods of time to maintain its remaining service life function.

When storing for more than three months, store within an ambient 
temperature range of 

25 to +30°C and the humidity range of 25% 

to 70%.

Periodic Check (S8VS-09024

@@

, S8VS-

12024

@@

, S8VS-18024

@@

, S8VS-

24024

@@

, and S8VS-48024

@

only)

It may take from several years to more than 10 years under general 
operating conditions for the power supply to output the maintenance 
forecast monitor alarm (S8VS-

@@@

24A

@

). The total run time 

monitor (S8VS-

@@@

24B

@

) may be a similar number of years as the 

maintenance forecast monitor according to some settings. During 
operation over an extended period of time, periodically check if the 
maintenance forecast monitor output (Yrs) or total run time monitor 
output (kh) is correctly functioning by the following procedure.

1.

Select the operation mode.

2.

Check that the output (Yrs/kh) is turned ON (with continuity).

3.

In the operation mode, press and hold the Down Key 

D

 (10) and 

the Mode Key 

M

 (8) simultaneously for at least three seconds.

The main display (6) changes to “

a02

.”

An inactive output (Yrs/kh) (no continuity) in the “

a02

” indication 

indicates the correct function.

4.

Release keys to return to the regular state.

Note:

DC output stays ON during the periodical check.

Overcurrent Protection

Internal parts may possibly deteriorate or be damaged if a 
short-circuited or overcurrent state continues during operation. 

Internal parts may possibly deteriorate or be damaged if the Power 
Supply is used for applications with frequent inrush current or 
overloading at the load end. Do not use the Power Supply for such 
applications.

Alarm Output (S8VS-09024

@@

,

S8VS-12024

@@

, S8VS-18024

@@

,

S8VS-24024

@@

, and S8VS-48024

@

Only)

When using the alarm output, sufficiently consider the maximum 
ratings, residual voltage, and leakage current. 

Transistor output:

Sinking for S8VS-

@@@

24

@

 models

Sourcing for S8VS-

@@@

24

@

P models

Sinking/Sourcing for S8VS-48024A/B models

30 VDC max., 50 mA max.
ON residually voltage:

2 V max.

OFF leakage current:

0.1 mA max.

Dielectric Strength Test

If a high voltage is applied between an input and the case (FG), it will 
pass though the LC of the built-in noise filter and energy will be 
stored. If the high voltages used for dielectric strength testing are 
turned ON and OFF with a switch, timer, or similar device, impulse 
voltage will be generated when the voltage is turned OFF and 
internal parts may possibly be damaged. To prevent the generation 
of impulse voltages, reduce the applied voltage slowly with a variable 
resistor on the test device or turn the voltage ON and OFF at the 
zero-cross point. 

1

13

(COMMON)

12

(Yrs/kh)

11

(DC LOW)

2

4

5

8

9

7

6

10

3

60-, 90- , 120-, 
180-, 240-W 
Models

13

11

4

5

8

9

7

12

6

10

14

15

16

3

1

2

(Yrs/kh)

(DC LOW)

480-W Models

http://www.ia.omron.com/

27

(c)Copyright OMRON Corporation 2007   All Rights Reserved. 

Summary of Contents for S8VS Series

Page 1: ...05 Teil 1 15 30 W Models Compact Thin Power Supplies That Mount Just About Anywhere to Contribute to Control Panel Downsizing Compact thin size 22 5 85 96 5 mm W H D Three mounting directions standard...

Page 2: ...0 W models 1 2 3 4 S8VS 1 Power Ratings 015 15 W 030 30 W 060 60 W 090 90 W 120 120 W 180 180 W 240 240 W 480 480 W 2 Output voltage 05 5 V 12 12 V 24 24 V 3 Indication monitor None Without indication...

Page 3: ...0 A Peak current 30 A 200 VAC S8VS 48024 Power ratings Input voltage Output voltage Output current Alarm output Model number 60 W 100 to 240 VAC 24 V 2 5 A S8VS 06024A 90 W 3 75 A Sinking S8VS 09024A...

Page 4: ...in at rated input output voltage Additional functions Overload protection See note 2 105 to 160 of rated load current voltage drop automatic reset 105 to 160 of rated load current voltage drop intermi...

Page 5: ...ted load current voltage drop intermittent automatic reset Overvoltage protection See notes 2 and 4 Yes Output voltage indication See note 5 No Yes selectable See note 6 No Yes selectable See note 6 O...

Page 6: ...le Total run time monitor output See note 5 No Yes transistor out put 30 VDC max 50 mA max See note 9 No Yes transistor out put 30 VDC max 50 mA max See note 9 Undervoltage alarm indication See note 5...

Page 7: ...age alarm output terminals No Yes transistor output 30 VDC max 50 mA max See note 9 No Yes transistor output 30 VDC max 50 mA max See note 9 Parallel operation No Series operation Yes for up to 2 Powe...

Page 8: ...r smoothing circuit Noise filter AC L INPUT AC N Drive control circuit DC OUTPUT Fuse 3 15 A Overcurrent circuit Current detection circuit Arithmetic operation circuit Display circuit Switch Overvolta...

Page 9: ...S 18024BP Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit Rectifier smoothing circuit Arithmet...

Page 10: ...oothing circuit Rectifier smoothing circuit Photocoupler Display circuit Switch Harmonic current suppression Smoothing Inrush current protection circuit Voltage detection circuit Overvoltage detection...

Page 11: ...ways ground this terminal No Name Function 1 AC Input terminals L N Connect the input lines to these terminals See note 1 2 Protective Earth terminal PE Connect the ground line to this terminal See no...

Page 12: ...d output voltage To reset the power supply leave the power supply off for more than 3 minutes and then turn it on again Note 1 Do not turn ON the power again until the cause of the overvoltage has bee...

Page 13: ...a direct current DC output is ON 5 Output voltage adjuster V ADJ Use to adjust the voltage 6 Main display Red See note 3 Indicates the measurement or set value 7 Operation indicator Orange See note 3...

Page 14: ...ecast monitor Blinks during setup of maintenance forecast monitor setting S8VS 48024A kh Lights up during indication of total run time monitor Blinks during setup of total run time monitor S8VS 48024B...

Page 15: ...ting mode Press and hold Up key U or Down Key D for three seconds or more Output voltage Voltage output by Power Supply is monitored and displayed Output current Current output by Power Supply is moni...

Page 16: ...indicated Press Key output load indication When the maintenance forecast monitor or overheat alarm is indicated Press Key undervoltage alarm indication 2 The above displays are for models with a main...

Page 17: ...atic reset No change e01 Undervoltage alarm set value memory error Undervoltage output terminal DC LOW turns OFF Press and hold the Up Key U 9 or Down Key D 10 for three seconds and check the set valu...

Page 18: ...etting is less than 2 0 years the indication changes to a value 1 5 after the remaining time becomes less than two years and after the remaining time becomes less than the set time an alarm a02 and th...

Page 19: ...nance forecast monitor are not issued 2 The maintenance forecast is accelerated or decelerated according to operating conditions Periodically check indication 3 Acceleration or deceleration of the mai...

Page 20: ...lue reached OFF i e no continuity at the total run time output terminal kh The alarm set value can be changed in the setting mode Example Alarm Displays When a Total Run Time Set Value of 88 kh Is Rea...

Page 21: ...8VS 48024 only The peak current must satisfy the following conditions Input voltage range 200 to 240 VAC Peak current value 30 A max Peak current pulse width 2 s max Cycle 60 s min Note 1 Two seconds...

Page 22: ...ince the AC power is supplied 2 The alarm is not indicated in the setting mode 3 Press the Mode Key 8 after the output voltage is restored to reset alarm indication 4 The undervoltage alarm function m...

Page 23: ...15 W S8VS 030 30 W 97 11 3 35 4 108 3 1 40 10 74 95 Five M4 with square washer Rail stopper 4 5 Sliding 15 max S8VS 06024 60 W S8VS 06024 60 W 110 5 10 8 34 9 121 3 1 94 115 10 50 Five M4 with square...

Page 24: ...M4 with square washer Rail stopper 4 5 Sliding 15 max Rail stopper Screwless block 2 5 mm pitches S8VS 24024 240 W S8VS 24024 240 W S8VS 48024 480 W S8VS 48024 480 W 10 70 Rail stopper Nine M4 with sq...

Page 25: ...els S82Y VS10S Side mounting Bracket For 180 W models S82Y VS15S Side mounting Bracket For 240 W models S82Y VS20S Front mounting Bracket For 60 90 120 180 and 240 W models S82Y VS10F 7 1 3 5 0 5 15 1...

Page 26: ...W 120 W 180 W 240 W and 480 W Models Note The rated current for output terminals is 10 A per terminal Be sure to use multiple terminals simultaneously for current that exceeds the terminal rating Inst...

Page 27: ...e main display 6 changes to a02 An inactive output Yrs kh no continuity in the a02 indication indicates the correct function 4 Release keys to return to the regular state Note DC output stays ON durin...

Page 28: ...n series the current flowing through the load must not exceed the smaller rated output current 3 Serial operation is not possible with 5 V and 12 V models Parallel Operation The Product is not designe...

Page 29: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syst...

Reviews: