S8VS

Maintenance Forecast Monitor Function 

The Power Supply is equipped with electrolytic capacitors.

The electrolyte inside the electrolytic capacitor penetrates the 
sealing rubber and evaporates as time passes since it is 
manufactured, which causes deterioration of characteristics such as 
decreasing the capacitance, etc.

Due to this deterioration of the characteristics of the electrolytic 
capacitor, the Power Supply decreases its performance as time 
passes.

The maintenance forecast monitor function shows an approximate 
period left for maintenance of the Power Supply due to deterioration 
of electrolytic capacitors. When the period left for maintenance that 
the power supply forecasts reaches the set value, an alarm is 
indicated and an output signal is triggered.

Use this function to know the approximate replacement timing of the 
Power Supply.

Note:

The maintenance forecast monitor function indicates an 
approximate period left for maintenance, based on 
deterioration of the electrolytic capacitor. It does not predict 
failures caused by other reasons.

Relationship between Indicated Values and Output of Set Values

Principle of Operation

The deterioration speed of the electrolytic capacitor varies 
considerably according to the ambient temperature. (Generally the 
speed follows “Rule of Two for every 10°C”; for every 10°C increase 
in temperature the rate of degradation doubles according to 
Arrhenius’s equation.) The S8VS-

@@@

24A

@

 monitors the 

temperature inside the power supply, and calculates the amount of 
deterioration according to the running hours and inside temperature. 
Judging by this amount of deterioration, the power supply will give 
the alarm indication and output when the period left for maintenance 
reaches the set value.

Note: 1.

Due to degradation of internal electronic parts, replace the 
power supply approximately 15 years after purchase even if 
indication and output of maintenance forecast monitor are 
not issued.

2.

The maintenance forecast is accelerated or decelerated 
according to operating conditions. Periodically check 
indication.

3.

Acceleration or deceleration of the maintenance forecast 
may cause the output to repeatedly go ON/OFF.
Only the S8VS-09024A

@

, S8VS-12024A

@

, S8VS-

18024A

@

, S8VS-24024A

@

, and S8VS-48024A are 

equipped with output.

4.

The accuracy of the maintenance forecast function may be 
adversely affected by applications in which the AC input is 
frequently turned ON/OFF.

Reference Values 
(15-W to 480-W Models)

Note:

The maintenance forecast is the service life (the power supply’s 
internal temperature is monitored at all times) of the internal 
electrolytic capacitor in actual operating conditions, and varies 
according to the customer’s operating conditions. 15 years is 
taken as the maximum period of the maintenance forecast.

(L

0.5)

5.0

L=2.5

L=0.5

2.5

2.0

1.5

1.0

0.5

0

Initial capacity

"1.0" is displayed on the main display for the 
duration that the maintenance forecast up to 
replacement satisfies the condition 1.0 

≤ 

T

1.5.

In case of setting L between 2.5 and 5 years.

Maintenance forecast monitor output

T: Maintenance time 

until replacement

The numerical value 
decreases with time.

Main display

Capacity of Capacitor

Capacity level
at replacement

Note:

 This function can be set only on the S8VS-09024A

@,

S8VS-12024A

@,

S8VS-18024A

@,

S8VS-24024A

@

, and S8VS-48024A.

L: Maintenance forecast set value (See note.) 

0.0 to 5.0, 0.5 steps

Item

Value

Definition

Reliability 
(MTBF)

15 W to 240 W: 
135,000 hrs min.
480 W: 
60,000 hrs min.

MTBF stands for Mean Time 
Between Failures, which is 
calculated according to the 
probability of accidental device 
failures, and indicates reliability of 
devices.
Therefore, it does not necessarily 
represent the life of the Product.

Life 
expectancy

10 yrs. min.

The life expectancy indicates 
average operating hours under the 
ambient temperature of 40°C and a 
load rate of 50%. Normally this is 
determined by the life expectancy of 
the built-in aluminum electrolytic 
capacitor.

http://www.ia.omron.com/

19

(c)Copyright OMRON Corporation 2007   All Rights Reserved. 

Summary of Contents for S8VS Series

Page 1: ...05 Teil 1 15 30 W Models Compact Thin Power Supplies That Mount Just About Anywhere to Contribute to Control Panel Downsizing Compact thin size 22 5 85 96 5 mm W H D Three mounting directions standard...

Page 2: ...0 W models 1 2 3 4 S8VS 1 Power Ratings 015 15 W 030 30 W 060 60 W 090 90 W 120 120 W 180 180 W 240 240 W 480 480 W 2 Output voltage 05 5 V 12 12 V 24 24 V 3 Indication monitor None Without indication...

Page 3: ...0 A Peak current 30 A 200 VAC S8VS 48024 Power ratings Input voltage Output voltage Output current Alarm output Model number 60 W 100 to 240 VAC 24 V 2 5 A S8VS 06024A 90 W 3 75 A Sinking S8VS 09024A...

Page 4: ...in at rated input output voltage Additional functions Overload protection See note 2 105 to 160 of rated load current voltage drop automatic reset 105 to 160 of rated load current voltage drop intermi...

Page 5: ...ted load current voltage drop intermittent automatic reset Overvoltage protection See notes 2 and 4 Yes Output voltage indication See note 5 No Yes selectable See note 6 No Yes selectable See note 6 O...

Page 6: ...le Total run time monitor output See note 5 No Yes transistor out put 30 VDC max 50 mA max See note 9 No Yes transistor out put 30 VDC max 50 mA max See note 9 Undervoltage alarm indication See note 5...

Page 7: ...age alarm output terminals No Yes transistor output 30 VDC max 50 mA max See note 9 No Yes transistor output 30 VDC max 50 mA max See note 9 Parallel operation No Series operation Yes for up to 2 Powe...

Page 8: ...r smoothing circuit Noise filter AC L INPUT AC N Drive control circuit DC OUTPUT Fuse 3 15 A Overcurrent circuit Current detection circuit Arithmetic operation circuit Display circuit Switch Overvolta...

Page 9: ...S 18024BP Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit Rectifier smoothing circuit Arithmet...

Page 10: ...oothing circuit Rectifier smoothing circuit Photocoupler Display circuit Switch Harmonic current suppression Smoothing Inrush current protection circuit Voltage detection circuit Overvoltage detection...

Page 11: ...ways ground this terminal No Name Function 1 AC Input terminals L N Connect the input lines to these terminals See note 1 2 Protective Earth terminal PE Connect the ground line to this terminal See no...

Page 12: ...d output voltage To reset the power supply leave the power supply off for more than 3 minutes and then turn it on again Note 1 Do not turn ON the power again until the cause of the overvoltage has bee...

Page 13: ...a direct current DC output is ON 5 Output voltage adjuster V ADJ Use to adjust the voltage 6 Main display Red See note 3 Indicates the measurement or set value 7 Operation indicator Orange See note 3...

Page 14: ...ecast monitor Blinks during setup of maintenance forecast monitor setting S8VS 48024A kh Lights up during indication of total run time monitor Blinks during setup of total run time monitor S8VS 48024B...

Page 15: ...ting mode Press and hold Up key U or Down Key D for three seconds or more Output voltage Voltage output by Power Supply is monitored and displayed Output current Current output by Power Supply is moni...

Page 16: ...indicated Press Key output load indication When the maintenance forecast monitor or overheat alarm is indicated Press Key undervoltage alarm indication 2 The above displays are for models with a main...

Page 17: ...atic reset No change e01 Undervoltage alarm set value memory error Undervoltage output terminal DC LOW turns OFF Press and hold the Up Key U 9 or Down Key D 10 for three seconds and check the set valu...

Page 18: ...etting is less than 2 0 years the indication changes to a value 1 5 after the remaining time becomes less than two years and after the remaining time becomes less than the set time an alarm a02 and th...

Page 19: ...nance forecast monitor are not issued 2 The maintenance forecast is accelerated or decelerated according to operating conditions Periodically check indication 3 Acceleration or deceleration of the mai...

Page 20: ...lue reached OFF i e no continuity at the total run time output terminal kh The alarm set value can be changed in the setting mode Example Alarm Displays When a Total Run Time Set Value of 88 kh Is Rea...

Page 21: ...8VS 48024 only The peak current must satisfy the following conditions Input voltage range 200 to 240 VAC Peak current value 30 A max Peak current pulse width 2 s max Cycle 60 s min Note 1 Two seconds...

Page 22: ...ince the AC power is supplied 2 The alarm is not indicated in the setting mode 3 Press the Mode Key 8 after the output voltage is restored to reset alarm indication 4 The undervoltage alarm function m...

Page 23: ...15 W S8VS 030 30 W 97 11 3 35 4 108 3 1 40 10 74 95 Five M4 with square washer Rail stopper 4 5 Sliding 15 max S8VS 06024 60 W S8VS 06024 60 W 110 5 10 8 34 9 121 3 1 94 115 10 50 Five M4 with square...

Page 24: ...M4 with square washer Rail stopper 4 5 Sliding 15 max Rail stopper Screwless block 2 5 mm pitches S8VS 24024 240 W S8VS 24024 240 W S8VS 48024 480 W S8VS 48024 480 W 10 70 Rail stopper Nine M4 with sq...

Page 25: ...els S82Y VS10S Side mounting Bracket For 180 W models S82Y VS15S Side mounting Bracket For 240 W models S82Y VS20S Front mounting Bracket For 60 90 120 180 and 240 W models S82Y VS10F 7 1 3 5 0 5 15 1...

Page 26: ...W 120 W 180 W 240 W and 480 W Models Note The rated current for output terminals is 10 A per terminal Be sure to use multiple terminals simultaneously for current that exceeds the terminal rating Inst...

Page 27: ...e main display 6 changes to a02 An inactive output Yrs kh no continuity in the a02 indication indicates the correct function 4 Release keys to return to the regular state Note DC output stays ON durin...

Page 28: ...n series the current flowing through the load must not exceed the smaller rated output current 3 Serial operation is not possible with 5 V and 12 V models Parallel Operation The Product is not designe...

Page 29: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syst...

Reviews: