S8VS

Mounting

Note: 1.

Improper mounting will interfere with heat dissipation and 
may occasionally result in deterioration or damage of 
internal parts. Use the Product within the derating curve for 
the mounting direction that is used. Do not use the Power 
Supply mounted in any way not shown above. 

2.

Use a mounting bracket (S82Y-VS30P, sold separately) 
when the Product is mounted horizontally.

3.

Heat dissipation will be adversely affected. When the 
Product is mounted facing horizontally, always place the 
side with the label facing horizontally. 

4.

Use PFP-M End Plates on the top and bottom of the Power 
Supply when mounting horizontally on a DIN rail.

Overload Protection

The load and the power supply are automatically protected from 
overcurrent damage by this function.
Overload protection is activated if the output current rises above 
105% of the rated current.
When the output current returns within the rated range overload 
protection is automatically cleared.

Note: 1.

Internal parts may occasionally deteriorate or be damaged 
if a short-circuited or overcurrent state continues during 
operation. 

2.

Internal parts may possibly deteriorate or be damaged if the 
Power Supply is used for applications with frequent inrush 
current or overloading at the load end. Do not use the Power 
Supply for such applications.

Overvoltage Protection

Consider the possibility of an overvoltage and design the system so 
that the load will not be subjected to an excessive voltage even if the 
feedback circuit in the Power Supply fails.
This power supply automatically protects itself and the load from 
overvoltage.
Overvoltage protection is activated if the output voltage rises above 
approx. 130% of the rated output voltage. 
To reset the power supply, leave the power supply off for more than 3 
minutes and then turn it on again.

Note: 1.

Do not turn ON the power again until the cause of the 
overvoltage has been removed.

2.

The overvoltage protection of the S8VS-015

@@

 uses a 

zener diode clamp. The output voltage will be clamped at 
approx. 140% or higher of the rated output voltage (approx. 
140% to 190%). If the internal feedback circuit is destroyed 
by any chance, the load may be destroyed by the clamped 
output voltage (approx. 140% to 190% of the rated output 
voltage). The power Supply will not restart if the output is 
turned OFF by the overvoltage protection operation. If this 
occurs, replace the Power Supply.

Inrush Current, Startup Time, 
Output Hold Time

Undervoltage Alarm Indication

LED (DC LOW red) lights to warn of output voltage drop.

Detection voltage is set to approx. 80% (75 to 90%) of the rated 
output voltage.

Note:

This function monitors the voltage at the power supply output 
terminals. To check actual voltage, measure voltage on the load 
side.

Face-up mounting with DIN rail

S82Y-VS30P

Side with label

Horizontal mounting with S82Y-VS30P*

Standard mounting with DIN rail

Face-up mounting with S82Y-VS30P

Standard mounting with S82Y-VS30P

Note:

 The Side-mounting Bracket can be mounted from either side.

0

100

50

Output v

oltage (V)

Output current (%)

0

100

50

Output current (%)

Output v

oltage (V)

Intermittent 
operation

15-W Models

30-W Models

The values shown in the above diagrams are for reference only.

+15%

10%

0 V

+30%

(approx.)

Overvoltage protection 
operating

Variable range

Rated output

 voltage

Output v

oltage (V)

The values shown in the above diagram is for reference only.

90%

96.5%

Startup time (1,000 ms max.)

AC input
voltage

AC input
current

Output
voltage

Inrush current on input application

Input OFF

Input ON

Hold time 
(20 ms min.)

http://www.ia.omron.com/

12

(c)Copyright OMRON Corporation 2007   All Rights Reserved. 

Summary of Contents for S8VS Series

Page 1: ...05 Teil 1 15 30 W Models Compact Thin Power Supplies That Mount Just About Anywhere to Contribute to Control Panel Downsizing Compact thin size 22 5 85 96 5 mm W H D Three mounting directions standard...

Page 2: ...0 W models 1 2 3 4 S8VS 1 Power Ratings 015 15 W 030 30 W 060 60 W 090 90 W 120 120 W 180 180 W 240 240 W 480 480 W 2 Output voltage 05 5 V 12 12 V 24 24 V 3 Indication monitor None Without indication...

Page 3: ...0 A Peak current 30 A 200 VAC S8VS 48024 Power ratings Input voltage Output voltage Output current Alarm output Model number 60 W 100 to 240 VAC 24 V 2 5 A S8VS 06024A 90 W 3 75 A Sinking S8VS 09024A...

Page 4: ...in at rated input output voltage Additional functions Overload protection See note 2 105 to 160 of rated load current voltage drop automatic reset 105 to 160 of rated load current voltage drop intermi...

Page 5: ...ted load current voltage drop intermittent automatic reset Overvoltage protection See notes 2 and 4 Yes Output voltage indication See note 5 No Yes selectable See note 6 No Yes selectable See note 6 O...

Page 6: ...le Total run time monitor output See note 5 No Yes transistor out put 30 VDC max 50 mA max See note 9 No Yes transistor out put 30 VDC max 50 mA max See note 9 Undervoltage alarm indication See note 5...

Page 7: ...age alarm output terminals No Yes transistor output 30 VDC max 50 mA max See note 9 No Yes transistor output 30 VDC max 50 mA max See note 9 Parallel operation No Series operation Yes for up to 2 Powe...

Page 8: ...r smoothing circuit Noise filter AC L INPUT AC N Drive control circuit DC OUTPUT Fuse 3 15 A Overcurrent circuit Current detection circuit Arithmetic operation circuit Display circuit Switch Overvolta...

Page 9: ...S 18024BP Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit Rectifier smoothing circuit Arithmet...

Page 10: ...oothing circuit Rectifier smoothing circuit Photocoupler Display circuit Switch Harmonic current suppression Smoothing Inrush current protection circuit Voltage detection circuit Overvoltage detection...

Page 11: ...ways ground this terminal No Name Function 1 AC Input terminals L N Connect the input lines to these terminals See note 1 2 Protective Earth terminal PE Connect the ground line to this terminal See no...

Page 12: ...d output voltage To reset the power supply leave the power supply off for more than 3 minutes and then turn it on again Note 1 Do not turn ON the power again until the cause of the overvoltage has bee...

Page 13: ...a direct current DC output is ON 5 Output voltage adjuster V ADJ Use to adjust the voltage 6 Main display Red See note 3 Indicates the measurement or set value 7 Operation indicator Orange See note 3...

Page 14: ...ecast monitor Blinks during setup of maintenance forecast monitor setting S8VS 48024A kh Lights up during indication of total run time monitor Blinks during setup of total run time monitor S8VS 48024B...

Page 15: ...ting mode Press and hold Up key U or Down Key D for three seconds or more Output voltage Voltage output by Power Supply is monitored and displayed Output current Current output by Power Supply is moni...

Page 16: ...indicated Press Key output load indication When the maintenance forecast monitor or overheat alarm is indicated Press Key undervoltage alarm indication 2 The above displays are for models with a main...

Page 17: ...atic reset No change e01 Undervoltage alarm set value memory error Undervoltage output terminal DC LOW turns OFF Press and hold the Up Key U 9 or Down Key D 10 for three seconds and check the set valu...

Page 18: ...etting is less than 2 0 years the indication changes to a value 1 5 after the remaining time becomes less than two years and after the remaining time becomes less than the set time an alarm a02 and th...

Page 19: ...nance forecast monitor are not issued 2 The maintenance forecast is accelerated or decelerated according to operating conditions Periodically check indication 3 Acceleration or deceleration of the mai...

Page 20: ...lue reached OFF i e no continuity at the total run time output terminal kh The alarm set value can be changed in the setting mode Example Alarm Displays When a Total Run Time Set Value of 88 kh Is Rea...

Page 21: ...8VS 48024 only The peak current must satisfy the following conditions Input voltage range 200 to 240 VAC Peak current value 30 A max Peak current pulse width 2 s max Cycle 60 s min Note 1 Two seconds...

Page 22: ...ince the AC power is supplied 2 The alarm is not indicated in the setting mode 3 Press the Mode Key 8 after the output voltage is restored to reset alarm indication 4 The undervoltage alarm function m...

Page 23: ...15 W S8VS 030 30 W 97 11 3 35 4 108 3 1 40 10 74 95 Five M4 with square washer Rail stopper 4 5 Sliding 15 max S8VS 06024 60 W S8VS 06024 60 W 110 5 10 8 34 9 121 3 1 94 115 10 50 Five M4 with square...

Page 24: ...M4 with square washer Rail stopper 4 5 Sliding 15 max Rail stopper Screwless block 2 5 mm pitches S8VS 24024 240 W S8VS 24024 240 W S8VS 48024 480 W S8VS 48024 480 W 10 70 Rail stopper Nine M4 with sq...

Page 25: ...els S82Y VS10S Side mounting Bracket For 180 W models S82Y VS15S Side mounting Bracket For 240 W models S82Y VS20S Front mounting Bracket For 60 90 120 180 and 240 W models S82Y VS10F 7 1 3 5 0 5 15 1...

Page 26: ...W 120 W 180 W 240 W and 480 W Models Note The rated current for output terminals is 10 A per terminal Be sure to use multiple terminals simultaneously for current that exceeds the terminal rating Inst...

Page 27: ...e main display 6 changes to a02 An inactive output Yrs kh no continuity in the a02 indication indicates the correct function 4 Release keys to return to the regular state Note DC output stays ON durin...

Page 28: ...n series the current flowing through the load must not exceed the smaller rated output current 3 Serial operation is not possible with 5 V and 12 V models Parallel Operation The Product is not designe...

Page 29: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syst...

Reviews: