S8VS

Inrush Current

When two or more Power Supplies are connected to the same input, 
the total current is the sum of the currents for each Supply. Select 
fuses and circuit breakers giving sufficient consideration to the fusing 
or operating characteristics so that fuses will not burn and breakers 
will not break due to inrush current. 

Output Voltage Adjuster (V.ADJ)

The output voltage adjuster (V.ADJ) may possibly be damaged if it is 
turned with unnecessary force. Do not turn the adjuster with 
excessive force.

After completing output voltage adjustment, be sure that the output 
capacity or output current does not exceed the rated output capacity 
or rated output current.

15-W, 30-W Models

If the output voltage is set to a value less than 

10%, the 

undervoltage alarm function may operate.

60-W, 90-W, 120-W, 180-W, 240-W, and 480-W 
Models

If the output voltage is set to a value less than 20 V (the factory 
setting), the undervoltage alarm function may operate.

DIN Rail Mounting

To mount the Block on a DIN Rail, hook portion (A) of the Block onto 
the rail and press the Block in direction (B).

To dismount the Block, pull down portion (C) with a flat-blade 
screwdriver and pull out the Block.

Series Operation

(24-V Model)

Two power supplies can be connected in series.

Note: 1.

The diode is connected as shown in the figure. If the load is 
short-circuited, a reverse voltage will be generated inside 
the Power Supply. If this occurs the Power Supply may 
possibly deteriorate or be damaged. Always connect a 
diode as shown in the figure. 
Select a diode having the following ratings.

2.

Although Products having different specifications can be 
connected in series, the current flowing through the load 
must not exceed the smaller rated output current.

3.

Serial operation is not possible with 5-V and 12-V models.

Parallel Operation

The Product is not designed for parallel operation.

In Case There Is No Output Voltage

The possible cause for no output voltage may be that the overcurrent 
or overvoltage protection has operated. The internal protection may 
operate if a large amount of surge voltage such as a lightening surge 
occurs while turning ON the power supply.

In case there is no output voltage, please check the following points 
before contacting us:

Checking overload protected status:
Check whether the load is in overload status or is short-circuited. 
Remove wires to load when checking.

Checking overvoltage or internal protection (except for 15-W 
models):
Turn the power supply OFF once, and leave it OFF for at least 3 
minutes. Then turn it ON again to see if this clears the condition.

Buzzing Noise When the Input Is 
Turned ON

(120-W, 180-W, 240-W, and 480-W Models)

A harmonic current suppression circuit is built into the Power Supply. 
This circuit can create noise when the input is turned ON, but it will 
last only until the internal circuits stabilize and does not indicate any 
problem in the Product. 

(B)

(A)

(C)

30 mm min.

Track stopper

+V

V

+V

V

Correct

AC (L)

AC (N)

AC (L)

AC (N)

Type

Schottky Barrier diode

Dielectric strength 
(V

RRM

)

Twice the rated output voltage or 
above

Forward current 
(I

F

)

Twice the rated output current or 
above

+V

V

+V

V

Incorrect

AC (L)

AC (N)

AC (L)

AC (N)

In the interest of product improvement, specifications are subject to change without notice.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

http://www.ia.omron.com/

28

(c)Copyright OMRON Corporation 2007   All Rights Reserved. 

Summary of Contents for S8VS Series

Page 1: ...05 Teil 1 15 30 W Models Compact Thin Power Supplies That Mount Just About Anywhere to Contribute to Control Panel Downsizing Compact thin size 22 5 85 96 5 mm W H D Three mounting directions standard...

Page 2: ...0 W models 1 2 3 4 S8VS 1 Power Ratings 015 15 W 030 30 W 060 60 W 090 90 W 120 120 W 180 180 W 240 240 W 480 480 W 2 Output voltage 05 5 V 12 12 V 24 24 V 3 Indication monitor None Without indication...

Page 3: ...0 A Peak current 30 A 200 VAC S8VS 48024 Power ratings Input voltage Output voltage Output current Alarm output Model number 60 W 100 to 240 VAC 24 V 2 5 A S8VS 06024A 90 W 3 75 A Sinking S8VS 09024A...

Page 4: ...in at rated input output voltage Additional functions Overload protection See note 2 105 to 160 of rated load current voltage drop automatic reset 105 to 160 of rated load current voltage drop intermi...

Page 5: ...ted load current voltage drop intermittent automatic reset Overvoltage protection See notes 2 and 4 Yes Output voltage indication See note 5 No Yes selectable See note 6 No Yes selectable See note 6 O...

Page 6: ...le Total run time monitor output See note 5 No Yes transistor out put 30 VDC max 50 mA max See note 9 No Yes transistor out put 30 VDC max 50 mA max See note 9 Undervoltage alarm indication See note 5...

Page 7: ...age alarm output terminals No Yes transistor output 30 VDC max 50 mA max See note 9 No Yes transistor output 30 VDC max 50 mA max See note 9 Parallel operation No Series operation Yes for up to 2 Powe...

Page 8: ...r smoothing circuit Noise filter AC L INPUT AC N Drive control circuit DC OUTPUT Fuse 3 15 A Overcurrent circuit Current detection circuit Arithmetic operation circuit Display circuit Switch Overvolta...

Page 9: ...S 18024BP Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit Rectifier smoothing circuit Arithmet...

Page 10: ...oothing circuit Rectifier smoothing circuit Photocoupler Display circuit Switch Harmonic current suppression Smoothing Inrush current protection circuit Voltage detection circuit Overvoltage detection...

Page 11: ...ways ground this terminal No Name Function 1 AC Input terminals L N Connect the input lines to these terminals See note 1 2 Protective Earth terminal PE Connect the ground line to this terminal See no...

Page 12: ...d output voltage To reset the power supply leave the power supply off for more than 3 minutes and then turn it on again Note 1 Do not turn ON the power again until the cause of the overvoltage has bee...

Page 13: ...a direct current DC output is ON 5 Output voltage adjuster V ADJ Use to adjust the voltage 6 Main display Red See note 3 Indicates the measurement or set value 7 Operation indicator Orange See note 3...

Page 14: ...ecast monitor Blinks during setup of maintenance forecast monitor setting S8VS 48024A kh Lights up during indication of total run time monitor Blinks during setup of total run time monitor S8VS 48024B...

Page 15: ...ting mode Press and hold Up key U or Down Key D for three seconds or more Output voltage Voltage output by Power Supply is monitored and displayed Output current Current output by Power Supply is moni...

Page 16: ...indicated Press Key output load indication When the maintenance forecast monitor or overheat alarm is indicated Press Key undervoltage alarm indication 2 The above displays are for models with a main...

Page 17: ...atic reset No change e01 Undervoltage alarm set value memory error Undervoltage output terminal DC LOW turns OFF Press and hold the Up Key U 9 or Down Key D 10 for three seconds and check the set valu...

Page 18: ...etting is less than 2 0 years the indication changes to a value 1 5 after the remaining time becomes less than two years and after the remaining time becomes less than the set time an alarm a02 and th...

Page 19: ...nance forecast monitor are not issued 2 The maintenance forecast is accelerated or decelerated according to operating conditions Periodically check indication 3 Acceleration or deceleration of the mai...

Page 20: ...lue reached OFF i e no continuity at the total run time output terminal kh The alarm set value can be changed in the setting mode Example Alarm Displays When a Total Run Time Set Value of 88 kh Is Rea...

Page 21: ...8VS 48024 only The peak current must satisfy the following conditions Input voltage range 200 to 240 VAC Peak current value 30 A max Peak current pulse width 2 s max Cycle 60 s min Note 1 Two seconds...

Page 22: ...ince the AC power is supplied 2 The alarm is not indicated in the setting mode 3 Press the Mode Key 8 after the output voltage is restored to reset alarm indication 4 The undervoltage alarm function m...

Page 23: ...15 W S8VS 030 30 W 97 11 3 35 4 108 3 1 40 10 74 95 Five M4 with square washer Rail stopper 4 5 Sliding 15 max S8VS 06024 60 W S8VS 06024 60 W 110 5 10 8 34 9 121 3 1 94 115 10 50 Five M4 with square...

Page 24: ...M4 with square washer Rail stopper 4 5 Sliding 15 max Rail stopper Screwless block 2 5 mm pitches S8VS 24024 240 W S8VS 24024 240 W S8VS 48024 480 W S8VS 48024 480 W 10 70 Rail stopper Nine M4 with sq...

Page 25: ...els S82Y VS10S Side mounting Bracket For 180 W models S82Y VS15S Side mounting Bracket For 240 W models S82Y VS20S Front mounting Bracket For 60 90 120 180 and 240 W models S82Y VS10F 7 1 3 5 0 5 15 1...

Page 26: ...W 120 W 180 W 240 W and 480 W Models Note The rated current for output terminals is 10 A per terminal Be sure to use multiple terminals simultaneously for current that exceeds the terminal rating Inst...

Page 27: ...e main display 6 changes to a02 An inactive output Yrs kh no continuity in the a02 indication indicates the correct function 4 Release keys to return to the regular state Note DC output stays ON durin...

Page 28: ...n series the current flowing through the load must not exceed the smaller rated output current 3 Serial operation is not possible with 5 V and 12 V models Parallel Operation The Product is not designe...

Page 29: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syst...

Reviews: