40
External Tripping Input Function
Section 2-7
Tripping Trigger Type: Edge Trigger (EGE)
If the trigger signal (TRG) stays OFF for more than 10 ms and the branch out-
put is disconnected for more than 500 ms, the reset input can be received.
Tripping Trigger Type: Level Trigger (LVL)
a
Reset *
Branch output B voltage
(tripping input disabled)
Trigger signal
Branch output A voltage
(tripping input enabled)
10 ms
500 ms
a: 20 ms + Shutdown sequence setting time
*: Connected after startup sequence setting time has elapsed.
a
b
Branch output B voltage
(tripping input disabled)
Trigger signal
Branch output A voltage
(tripping input enabled)
a: 20 ms + Shutdown sequence setting time
b: 20 ms + Startup sequence setting time