![Omron S8AS User Manual Download Page 106](http://html1.mh-extra.com/html/omron/s8as/s8as_user-manual_743691106.webp)
88
CompoWay/F Communications Specifications
Section 6-1
6-1
CompoWay/F Communications Specifications
The S8AS-
@ @ @ @ @
R is equipped with an RS-485 port, which allows remote
monitoring and remote operations over networks, such as setting parameters,
connecting/disconnecting outputs, and clearing errors.
Connecting to the
Network
Refer to
3-4 RS-485 Port Wiring
for details on connecting the communications
cable.
Communications
Specifications
Communications cable
Connection configuration
1:n connection
Communications method
RS-485
Synchronization method
Start-stop synchronization
Baud rate
4,800 or 9,600 bps (Default value: 9,600 bps)
Transmission code
ASCII
Data length
7 or 8 bits (Default value: 7 bits)
Stop bits
1 or 2 bits (Default value: 2 bits)
Error detection
Vertical parity: None, even, or odd (Default value: Even)
BCC (block check character)
Flow control
None
Retry function
None