![Omron S8AS User Manual Download Page 118](http://html1.mh-extra.com/html/omron/s8as/s8as_user-manual_743691118.webp)
100
Variable Area Operations
Section 6-3
■
Response Codes
Write Variable Area
This service writes data to a variable area.
■
Service Request PDU
■
Service Response PDU
(1) Variable Type and Write Start Address
The definitions are different for each product.
(2) Bit Position
The S8AS does not support bit access. Fixed at “00.”
(3) Number of Elements
(4) Response Codes
Note
The “command too long” error does not occur with the Write Variable Area
command.
If data is written up to the number of elements specified in the service request
PDU, the error is processed as a number of elements/data mismatch error.
Response
code
Error name
Cause
Error
priority
1001
Command too long
The command is too long.
1
1002
Command too short
The command is too short.
2
1101
Area type error
The variable type is incorrect.
3
110B
Response too long
The number of elements is larger
than “0038.”
4
1100
Parameter error
The bit position is not “00.”
5
0000
Normal completion
No error
None
MRC SRC
0
1
0
2
0
0
2 2 2
4
2
4
Variable
Type
Write Start
Address
Bit
Position
Number of
Elements
Write Data
(for number of elements)
0 to 224
MRC SRC
0 1 0 2
2 2
4
Response Code
Number of
elements
Processing
0000
The write operation is not performed (does not append write
data to the service request PDU) and processing ends in “nor-
mal completion.”
0001 to 0038
The write operation is performed and processing ends in “nor-
mal completion” (hexadecimal display).
Response
code
Error name
Cause
Error
priority
1002
Command too short
The command is too short.
1
1101
Area type error
The variable type is incorrect.
2
1003
Number of ele-
ments/data mis-
match
The amount of data does not match
the number of elements.
3
1100
Parameter error
The bit position is not “00.” The write
data is out of the setting range.
4
0000
Normal completion
No error
None
Summary of Contents for S8AS
Page 1: ...S8AS Smart Power Supply USER S MANUAL Cat No Z269 E1 05...
Page 2: ......
Page 3: ...S8AS Smart Power Supply User s Manual Revised September 2013...
Page 4: ...iv...
Page 6: ...vi...
Page 104: ...86 Run Mode Section 5 4...
Page 128: ...110 ASCII List Section 6 10 6 10 ASCII List Even parity...
Page 144: ...126 Revision History...
Page 145: ......