103
Read Controller Attributes
Section 6-5
(3) Response Code
6-5
Read Controller Attributes
This service reads the model number and communications buffer size.
■
Service Request PDU
■
Service Response PDU
(1) Model
The first 10 bytes of ASCII data from the Read Controller Information com-
mand are returned. A specifications code follows the model number.
The following table shows the model number format.
(2) Buffer Size
The communications buffer size is expressed in 2-byte hexadecimal and is
converted to 4-byte ASCII before being displayed.
00F8 (Indicates 248 bytes.)
Response code
Error name
Cause
Error priority
1001
Command too long
The command is too long.
2
0000
Normal completion
No error
0
MRC SRC
0 5 0 3
2 2
MRC SRC
0 5 0 3
2 2
4
10
4
Response Code
Model
Buffer Size
Model
Code (4 bytes)
Same in all models
S8AS
−
Code (1 byte)
−
−
Capacity
Code (3 bytes)
240 W
240
480 W
480
Number of branch outputs
Code (2 bytes)
1
01
2
02
:
:
8
08
Communications specification
Code (1 byte)
No communications, settings can
be changed
All spaces
No communications, settings can-
not be changed
N
Communications, settings can be
changed
R
Remaining bytes
(9 bytes)
−
All spaces
Summary of Contents for S8AS
Page 1: ...S8AS Smart Power Supply USER S MANUAL Cat No Z269 E1 05...
Page 2: ......
Page 3: ...S8AS Smart Power Supply User s Manual Revised September 2013...
Page 4: ...iv...
Page 6: ...vi...
Page 104: ...86 Run Mode Section 5 4...
Page 128: ...110 ASCII List Section 6 10 6 10 ASCII List Even parity...
Page 144: ...126 Revision History...
Page 145: ......