4
Replace the complete Fan Unit.
1
3
2
(1) Push the lever
1
to unlock the Fan Unit.
(2) Lift the lever to tilt
2
the Fan Unit.
(3) Remove
3
the complete Fan Unit.
5
Insert the new Fan Unit in the Box PC.
Ensure the end of the Fan Unit
A
is positioned under the fan guide
B
.
B
A
6
Connect the Fan Connectors to the board.
7
Mount the Cover.
8
Power ON the system.
Confirm both fans rotate immediately after Power ON.
The fans are replaced and the alarm is automatically reset.
7 Maintenance
7 - 8
NY-series Industrial Box PC Without Operating System User's Manual (W586)