High Temperatures
Use the following cooling methods as required, taking into account the ambient temperature and the
amount of heating inside the panel.
Natural Cooling
Natural cooling relies on natural ventilation through slits in the panel, rather than using cooling devi-
ces such as fans or coolers. When using this method, observe the following points.
• Do not install the Box PC at the top of the panel, where hot air tends to stagnate.
• To provide ventilation space above and below the Box PC, leave sufficient distance from other
devices, wiring ducts, etc.
• Do not mount the Box PC in the wrong direction (e.g., vertically or upside down). Doing so may
cause abnormal heating in the Box PC.
• Do not install the Box PC directly above any heat-generating equipment, such as heaters or
transformers.
• Do not install the Box PC in a location exposed to direct sunlight.
Natural Cooling
OMRON
product
OMRON
product
Forced Ventilation
Forced ventilation with a fan in the top of the control cabinet.
Air filter
Fan
Forced Ventilation Method
OMRON
product
OMRON
product
Forced Air Circulation
Forced circulation with a fan inside the closed control cabinet.
5 Installation
5 - 17
NY-series Industrial Box PC Without Operating System User's Manual (W586)
5-3 Mount
5
5-3-3 T
emperature
Summary of Contents for NYB17-*100 SERIES
Page 8: ...CONTENTS 6 NY series Industrial Box PC Without Operating System User s Manual W586...
Page 30: ...Revision History 28 NY series Industrial Box PC Without Operating System User s Manual W586...
Page 40: ...1 Overview 1 8 NY series Industrial Box PC Without Operating System User s Manual W586...
Page 68: ...3 Software 3 4 NY series Industrial Box PC Without Operating System User s Manual W586...
Page 189: ...I Index I 1 NY series Industrial Box PC Without Operating System User s Manual W586 I...
Page 192: ......
Page 193: ......