Parallel Wiring (Single Phase)
Correct
Correct
Power supply
Incorrect
Power supply
Power supply
Load
Load
Load
Conduits
Conduits
Conduits
NG
OK
OK
• Power cables and signal cables adversely affect each other. Do not wire them in parallel.
• Noise induction may occur if the Box PC is installed in a panel that includes high-voltage devi-
ces. Wire and install them as far apart as possible.
• Either install the Box PC a minimum of 200 mm away from high-voltage lines or power lines, or
place the high-voltage lines or power lines in metal tubing and completely ground the metal tub-
ing to 100 Ω or less.
Example: Separating an OMRON product from Power Lines
Metal tubing
200 mm
200 mm
High-voltage power panel
Power lines
Power lines
Ground of
100 Ω or less
OMRON
product
OMRON
product
5 Installation
5 - 24
NY-series Industrial Box PC Without Operating System User's Manual (W586)