• Power cables and signal cables adversely affect each other. Do not wire them in parallel.
• Noise induction may occur if the Panel PC is installed in a panel that includes high-voltage devi-
ces. Wire and install them as far apart as possible.
• Either install the Panel PC a minimum of 200 mm away from high-voltage lines or power lines, or
place the high-voltage lines or power lines in metal tubing and completely ground the metal tub-
ing to 100 Ω or less.
Example: Separating an OMRON product from Power Lines
Metal tubing
200 mm
200 mm
High-voltage power panel
Power lines
Power lines
Ground of
100 Ω or less
OMRON
product
OMRON
product
l
Wiring Ducts
Whenever possible, route the cables and wires through wiring ducts.
Install the wiring ducts so that it is easy to route the wires from the IPC Machine Controller directly
into the duct.
Additional Information
Refer to
on page 5 - 15 for the minimum required distances.
It is convenient to use wiring ducts that have the same depth as the IPC Machine Controller.
Duct
Product
5 Installation
5 - 22
NY-series Industrial Panel PC Hardware User's Manual (W557)
Summary of Contents for NY532-1*00-111*13**0
Page 42: ...Sections in this Manual 40 NY series Industrial Panel PC Hardware User s Manual W557...
Page 86: ...3 Hardware Overview 3 28 NY series Industrial Panel PC Hardware User s Manual W557...
Page 160: ...5 Installation 5 48 NY series Industrial Panel PC Hardware User s Manual W557...
Page 208: ...Appendices A 16 NY series Industrial Panel PC Hardware User s Manual W557...
Page 209: ...I Index I 1 NY series Industrial Panel PC Hardware User s Manual W557 I...
Page 212: ......
Page 213: ......