Daisy Chain
This is an earthing method to connect the device that is connected with a communications cable, other
devices, and a device that could be a noise source using a daisy-chain topology to a common earth
electrode.
This earthing method is not recommended because the device that could be a noise source may inter-
fere electromagnetically with other devices.
Hub
Control panel
Other device
A device that could be
a noise source
NY-series
Industrial Box PC
NY-series
Industrial Panel PC
NY-series
Industrial Monitor
5 Installation
5 - 31
NY-series Industrial Panel PC Hardware User's Manual (W557)