3 Configuration Units
3 - 6
NX-series CPU Unit Hardware User’s Manual (W535)
Precautions for Safe Use
• Do not turn OFF the power supply to the Controller while the BUSY indicator flashes. While
the BUSY indicator is lit, the user program and settings in the CPU Unit are being backed up
in the built-in non-volatile memory. The data will not be backed up if the power supply is
turned OFF. The next time that the Controller is started, a Controller error in the major fault
level will occur and operation will stop.
• Do not turn OFF the power supply or remove the SD Memory Card while SD Memory Card
access is in progress (i.e., while the SD BUSY indicator flashes). Data may become cor-
rupted, and the Controller will not operate correctly if it uses corrupted data. To remove an
SD Memory Card from the CPU Unit when power is supplied to the CPU Unit, press the SD
Memory Card power supply switch and wait for the SD PWR indicator to turn OFF before you
remove the SD Memory Card.
You can check the operation status of the CPU Unit with the PWR, RUN, and ERROR indicators at
the top of the front panels of the Power Supply Unit and CPU Unit.
Refer to
5-1 Overview of Troubleshooting
on page 5-2 for the procedures to check the operation sta-
tus of the CPU Unit.
Indicators at the Bottom
These indicators show the operation status of the built-in ports of the CPU Unit.
Port 1 and port 2 are the indicators for the built-in EtherNet/IP ports, while port 3 is the indicators for
the built-in EtherCAT port.
• Built-in EtherNet/IP Ports (Port 1 and Port 2) Indicators
Indicator
Color
Status
Meaning
NET RUN
Green
Not lit.
You cannot perform Ethernet communications.
• The power supply is OFF or the CPU Unit was reset.
• A MAC address error or communications Controller error
occurred.
Flashing Ethernet communications are in progress.
• Tag data link connection establishment in progress.
• IP address acquisition with BOOTP in progress.
Lit.
Normal startup status.
NET RUN
PORT1
EtherNet/IP
NET ERR
LINK/ACT
NET RUN
PORT2
EtherNet/IP
PORT3
EtherCAT
NET ERR
LINK/ACT
NET RUN
NET ERR
LINK/ACT
Built-in
EtherCAT port
indicators
Built-in
EtherNet/IP port
indicators
Summary of Contents for NX701-1620
Page 11: ...9 Manual Structure NX series CPU Unit Hardware User s Manual W535...
Page 46: ...Sections in this Manual 44 NX series CPU Unit Hardware User s Manual W535...
Page 64: ...1 Introduction to NX series Controllers 1 18 NX series CPU Unit Hardware User s Manual W535...
Page 72: ...2 System Configuration 2 8 NX series CPU Unit Hardware User s Manual W535...
Page 90: ...3 Configuration Units 3 18 NX series CPU Unit Hardware User s Manual W535...
Page 156: ...6 Inspection and Maintenance 6 14 NX series CPU Unit Hardware User s Manual W535...
Page 163: ...I 1 I NX series CPU Unit Hardware User s Manual W535 Index...
Page 166: ...I 4 NX series CPU Unit Hardware User s Manual W535 Index...
Page 167: ......