K8DT-TH
7
DIP Switch Functions
K8DT-TH1
Note:
The default setting is 0°C.
Note:
All pins are set to OFF by default.
K8DT-TH2
Note:
The default setting is 0°C.
Note:
All pins are set to OFF by default.
R_SW3
100°C/°F units (0 to 9)
R_SW2
10°C/°F units (0 to 9)
R_SW1
1°C/°F units (0 to 9)
PIN
ON
❍
↑
OFF
●
↓
Alarm Mode
Upper limit
●
---
---
---
---
---
---
Not used.
Lower limit
❍
---
---
---
---
---
---
Latching
With latching
---
●
---
---
---
---
---
Without latching
---
❍
---
---
---
---
---
Output drive
method
Normally open
---
---
●
---
---
---
---
Normally closed
---
---
❍
---
---
---
---
Temperature
unit
°C
---
---
---
●
---
---
---
°F
---
---
---
❍
---
---
---
Input type
K
---
---
---
---
●
●
●
J
---
---
---
---
●
●
❍
T
---
---
---
---
●
❍
●
E
---
---
---
---
●
❍
❍
Pt100
---
---
---
---
❍
●
●
Pt1000
---
---
---
---
❍
●
❍
NOT USE
---
---
---
---
❍
❍
●
NOT USE
---
---
---
---
❍
❍
❍
R_SW3
1,000°C/°F units (0 to 3)
Note:
A temperature setting error occurs if this switch
is set to a value from 4 to 9.
R_SW2
100°C/°F units (0 to 9)
R_SW1
10°C/°F units (0 to 9)
PIN
ON
❍
↑
OFF
●
↓
Alarm Mode
Upper limit
●
---
---
---
---
---
---
Not used.
Lower limit
❍
---
---
---
---
---
---
Latching
With latching
---
●
---
---
---
---
---
Without latching
---
❍
---
---
---
---
---
Output drive
method
Normally open
---
---
●
---
---
---
---
Normally closed
---
---
❍
---
---
---
---
Temperature
unit
°C
---
---
---
●
---
---
---
°F
---
---
---
❍
---
---
---
Input type
K
---
---
---
---
●
●
●
J
---
---
---
---
●
●
❍
T
---
---
---
---
●
❍
●
E
---
---
---
---
●
❍
❍
B
---
---
---
---
❍
●
●
R
---
---
---
---
❍
●
❍
S
---
---
---
---
❍
❍
●
PL II
---
---
---
---
❍
❍
❍
1
ON
OFF
2
3
4
5
6
7
8
1
ON
OFF
2
3
4
5
6
7
8