background image

K8DT-TH

2

Ratings and Specifications

Ratings

Specifications

*

Industrial Electromagnetic Environment (EN/IEC 61326-1, Table 2)

Power supply 
voltage

K8DT-TH

@@

D: 24 VAC 50/60 Hz or 24 VDC

K8DT-TH

@@

A: 100 to 240 VAC 50/60 Hz

Allowable voltage 
range

85% to 110% of power supply voltage

Power 
consumption

24 VAC or 24 VDC: 2.1 VA max. or 1.2 W max.
100 to 240 VAC: 3.1 VA max.

Rated insulation 
voltage

253 VAC

Sensor 
inputs

K8DT-TH1

Thermocouple: K, J, T, E; 
Platinum-resistance thermometer: Pt100, Pt1000

K8DT-TH2

Thermocouple: K, J, T, E, B, R, S, PL II

Setting method

Set of three rotary DIP switches

Indicators

Power (PWR): Green, 
Alarm (ALM): Red

Output form

Relay Output: SPDT contact
Transistor Output: 1

Output relay 
ratings

Rated load

5 A at 250 VAC (Resistive load)
5 A at 30 VDC (Resistive load)
1 A at 250 VAC (Inductive load)
0.2 A at 48 VDC (Inductive load)

Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 

operations
3 A at 250 VAC/30 VDC: 100,000 
operations

Transistor output 
ratings

Rated voltage: 24 VDC (maximum voltage: 26.4 VDC)
Maximum current: 50 mA DC

Ambient operating 
temperature

20 to 60°C (with no condensation or icing)

Storage 
temperature

25 to 65°C (with no condensation or icing)

Ambient operating 
humidity

25% to 85% RH (with no condensation)

Storage humidity

25% to 85% RH (with no condensation)

Altitude

2,000 m max.

Applicable wires

Stranded wires, solid wires, or ferrules

Applicable wire 
size

0.25 to 1.5 mm

2

 (AWG24 to AWG16)

Wire insertion force

8 N max. for AWG20 wire

Screwdriver 
insertion force

15 N max.

Wire stripping 
length

8 mm

Ferrule length

8 mm

Recommended flat-
blade screwdriver

XW4Z-00B (Omron)
SZF 0.4   2.5 (Phoenix Contact)
210-719 (Wago)
SDI 0.4 

 

2.5 

 

75 (Weidmuller)

Current capacity

10 A (per pole)

Number of 
insertions

50 times

Case color

N1.5

Case material

PC, UL 94 V-0

Weight

Approx. 100 g

Mounting

Mounts to DIN Track, or screw mounting

Dimensions

17.5   90   90 mm (W D H)

Measurement 
accuracy

K8DT-TH1

@@

: ±1% of the setting range or ±4 °C, 

whichever is larger.
K8DT-TH2

@@

: ±1% of the setting range (±1%FS).

Hysteresis width

2°C 

Sampling cycle

100 ms

Applicable 
standards

Approved 
standards

EN 61010-1
Installation environment: 
Overvoltage category II, pollution level 2

EMC

EN 61326-1 

*

Safety 
standards

UL 61010-1 (Listing)
Korean Radio Waves Act (Act 10564)

Insulation resistance

20 M  min.

Between all external terminals and the case
Between all power supply terminals and all input 
terminals
Between all power supply terminals and all output 
terminals
Between all input terminals and all output 
terminals

Dielectric strength

3,000 VAC for 1 min

Between all external terminals and the case
Between all power supply terminals and all input 
terminals
Between all power supply terminals and all output 
terminals
Between all input terminals and all output 
terminals

Impulse withstand 
voltage

6 kV (between live terminals and exposed, 
non-charged metal parts)

Noise immunity

Square-wave noise of 1  s/100 ns pulse width with 
1-ns rise time
100 to 240 VAC: 1,500 V power supply terminal 
common/normal mode
24 VAC: 1,500 V power supply terminal common/
normal mode
24 VDC: 480 V power supply terminal common

Vibration resistance

Frequency: 10 to 55 Hz, 0.35-mm single amplitude
10 sweeps of 5 min each in X,Y, and Z directions

Shock resistance

100 m/s

2

, 3 times each in 6 directions along 3 axes

Degree of protection

Terminals: IP20

Summary of Contents for K8DT-TH

Page 1: ...Models added with transistor outputs for superior contact reliability Ordering Information Temperature Input Models Refer to Setting Ranges on page 3 for the setting ranges Options Order Separately Fr...

Page 2: ...length 8 mm Ferrule length 8 mm Recommended flat blade screwdriver XW4Z 00B Omron SZF 0 4 2 5 Phoenix Contact 210 719 Wago SDI 0 4 2 5 75 Weidmuller Current capacity 10 A per pole Number of insertions...

Page 3: ...0 400 100 0 0 0 0 0 0 0 Minimum setting increment 10 C Input K J T E B R S PL II Setting temperature range 3 200 3 100 3 000 2 900 2 800 2 700 2 600 2 500 2 400 2 300 2 200 2 100 2 000 1 900 1 800 1 7...

Page 4: ...DIP SW Inside Inside 2 Output C Relay Output T Transistor Output 14 11 12 14 11 3 Power supply voltage A 100 to 240 VAC D 24 VAC VDC No polarity A1 A2 A1 A2 Relay output normally closed 11 to 14 Relay...

Page 5: ...not resume normal operation it must be replaced Latching and the SV Protect Mode are stored in non volatile memory An error may occur if the data is updated more than one million times If you press a...

Page 6: ...11 Sinking In the case of sinking output applications 14 load K8DT 11 In the case of sourcing output applications 14 Sourcing O N 1 2 3 4 5 6 7 8 SW3 DIP Switch SW2 SW1 SW4 SW7 SW6 SW5 SW8 Turn OFF th...

Page 7: ...g Without latching Output drive method Normally open Normally closed Temperature unit C F Input type K J T E Pt100 Pt1000 NOT USE NOT USE R_SW3 1 000 C F units 0 to 3 Note A temperature setting error...

Page 8: ...17 5 90 86 90 5 100 Temperature Monitoring Relay K8DT TH Options Order Separately Front Cover Y92A D1A 52 7 3 5 1 8 17 5 5 85 DIN Tracks PFP 100N PFP 50N Dimensions in parentheses are for the PFP 50N...

Page 9: ...lay take appropriate safety measures such as installing a monitoring device on a separate line Use of the product beyond its life may result in contact welding or burning Make sure to consider the act...

Page 10: ...ndustrial waste 21 Make sure the indicators operate correctly Depending on the application environment the indicators may deteriorate prematurely and become difficult to see 22 The maximum terminal te...

Page 11: ...at it will not come off and the wire is securely fastened to the terminal block If you use a ferrule with a conductor length of 10 mm part of the conductor may be visible after the ferrule is inserted...

Page 12: ...ulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic insulation between the input terminals a...

Page 13: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 14: ...9 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyo...

Page 15: ...0HZ GCA32A240VAC50 60HZ GCA32A48VAC60HZ GCA63A120VAC50 60HZ GCA63A208VAC60HZ GCA63A220VAC60HZ GCA63A230VAC50 60HZ GCA63A240VAC50 60HZ GCA63A277VAC60HZ GCA63A48VAC60HZ GCA63A500VAC50 60HZ GCA63A600VAC6...

Reviews: