K8DT-TH

4

Connections

Terminal Diagram

Note: 1.

Do not connect anything to terminals that are shaded in gray.

2.

There is no polarity for the DC power supply input.

Timing Charts

Functions

SV Protection

This function protects (i.e., prohibits changing) the alarm setting, 
operating method, and modes for the Temperature Monitoring Relay 
that have been set on the rotary switches and DIP switch.
The protection function is activated by pressing the output latch reset 
button on the Temperature Monitoring Relay for at least 5 s. The 
power indicator will flash when the protection is activated.
The protection function can be released by pressing the output latch 
reset button on the Temperature Monitoring Relay for at least 5 s. The 
power indicator will light while the protection is being reset.

(1) Temperature sensor input

TH1

TH2

K8DT-TH1 C A

(1) (2)(3)

B

+

B

B

A

A

B

B

+

+

B

A1

B

+

14

A2

A

11

12

B

DIP SW

Inside

Inside

(2) Output

C: Relay Output

T: Transistor Output

14

11

12

14

11

(3) Power supply voltage

A: 100 to 240 VAC

D: 24 VAC/VDC

(No polarity)

A1

A2

A1

A2

Relay output (normally closed) 
(11) to (14)

Relay output (normally open) 
(11) to (14)

Temperature alarm or other error

Power supply

Relay output (latched) 
(11) to (14)

LATCH_RESET

Temperature alarm or other error

Power supply

PWR_LED

SV Protect Mode

Power supply

ALM_LED

Temperature alarm

Power supply

Other error

Temperature alarm lower limit 
(11) to (14)

Temperature alarm upper limit 
(11) to (14)

Temperature settings

Note: Other errors: sensor open circuit error, sensor input error, 

temperature setting error, and memory error.

0.02 s

2°C (°F)

2°C (°F)

Flashing

Flashing

Note: If LATCH_RESET is enabled, alarm status will be retained even if the power supply is cycled.

To clear the alarm status, press the LATCH_RESET button.
(Default: Latching enabled.)

Temperature Alarm: Hysteresis: 2°C or 2°F

Changing between Normally Open and Normally Closed

Latched Operation: 
Relay outputs remain latched even after the alarm or error is reset.

Operation of Indicators

Summary of Contents for K8DT-TH

Page 1: ...Models added with transistor outputs for superior contact reliability Ordering Information Temperature Input Models Refer to Setting Ranges on page 3 for the setting ranges Options Order Separately Fr...

Page 2: ...length 8 mm Ferrule length 8 mm Recommended flat blade screwdriver XW4Z 00B Omron SZF 0 4 2 5 Phoenix Contact 210 719 Wago SDI 0 4 2 5 75 Weidmuller Current capacity 10 A per pole Number of insertions...

Page 3: ...0 400 100 0 0 0 0 0 0 0 Minimum setting increment 10 C Input K J T E B R S PL II Setting temperature range 3 200 3 100 3 000 2 900 2 800 2 700 2 600 2 500 2 400 2 300 2 200 2 100 2 000 1 900 1 800 1 7...

Page 4: ...DIP SW Inside Inside 2 Output C Relay Output T Transistor Output 14 11 12 14 11 3 Power supply voltage A 100 to 240 VAC D 24 VAC VDC No polarity A1 A2 A1 A2 Relay output normally closed 11 to 14 Relay...

Page 5: ...not resume normal operation it must be replaced Latching and the SV Protect Mode are stored in non volatile memory An error may occur if the data is updated more than one million times If you press a...

Page 6: ...11 Sinking In the case of sinking output applications 14 load K8DT 11 In the case of sourcing output applications 14 Sourcing O N 1 2 3 4 5 6 7 8 SW3 DIP Switch SW2 SW1 SW4 SW7 SW6 SW5 SW8 Turn OFF th...

Page 7: ...g Without latching Output drive method Normally open Normally closed Temperature unit C F Input type K J T E Pt100 Pt1000 NOT USE NOT USE R_SW3 1 000 C F units 0 to 3 Note A temperature setting error...

Page 8: ...17 5 90 86 90 5 100 Temperature Monitoring Relay K8DT TH Options Order Separately Front Cover Y92A D1A 52 7 3 5 1 8 17 5 5 85 DIN Tracks PFP 100N PFP 50N Dimensions in parentheses are for the PFP 50N...

Page 9: ...lay take appropriate safety measures such as installing a monitoring device on a separate line Use of the product beyond its life may result in contact welding or burning Make sure to consider the act...

Page 10: ...ndustrial waste 21 Make sure the indicators operate correctly Depending on the application environment the indicators may deteriorate prematurely and become difficult to see 22 The maximum terminal te...

Page 11: ...at it will not come off and the wire is securely fastened to the terminal block If you use a ferrule with a conductor length of 10 mm part of the conductor may be visible after the ferrule is inserted...

Page 12: ...ulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic insulation between the input terminals a...

Page 13: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 14: ...9 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyo...

Page 15: ...0HZ GCA32A240VAC50 60HZ GCA32A48VAC60HZ GCA63A120VAC50 60HZ GCA63A208VAC60HZ GCA63A220VAC60HZ GCA63A230VAC50 60HZ GCA63A240VAC50 60HZ GCA63A277VAC60HZ GCA63A48VAC60HZ GCA63A500VAC50 60HZ GCA63A600VAC6...

Reviews: