K8DT-TH
6
Operation Method
Connections
Outputs
For a relay output, the SPDT contacts are output on terminals 11, 12, and 14. For a transistor output, the output is on terminals 11 and 14.
The internal circuit of the transistor output is NPN, but application is possible for either a sinking or sourcing output.
DIP Switch Settings
load
K8DT
11
Sinking
In the case of sinking output applications
14
load
K8DT
11
In the case of sourcing output applications
14
Sourcing
O
N
1
2
3
4
5
6
7
8
SW3
DIP Switch
SW2
SW1
SW4
SW7
SW6
SW5
SW8
Turn OFF the power to the Temperature Monitoring Relay before
you change the DIP switch settings.
The DIP switch settings take effect when the power is turned ON.
Use a flat-blade screwdriver to set the DIP switch pins.
Note:
Open the DIP switch cover to set the DIP switch.
Keep the DIP switch cover closed while the power supply to the Relay is ON.