Cat. No. N146-E1-02

Three-phase Phase-sequence Phase-loss Relay

 K8AB-PM

5

Nomenclature

Front

Indicators

Note:

The input across L1 and L2 is used for the internal power 
supply. Therefore, the power indicator will not be lit if there is no 
input across L1 and L2.

Setting Knobs

Note: 1.

Use either a solid wire of 2.5 mm

2

 maximum or a ferrule with 

insulating sleeve for the terminal connection.
The length of the exposed current-carrying part inserted 
into the terminal must be 8 mm or less to maintain dielectric 
strength after connection. 

Recommended ferrules

Phoenix Contact

Al 1,5-8BK (for AWG16)

Al 1-8RD (for AWG18)

Al 0,75-8GY (for AWG18)

2.

Tightening torque
Recommended: 0.49 N·m
Maximum: 0.54 

N·m

Power indicator

Relay status indicator

Overvoltage knob
(OVER)

Undervoltage knob
(UNDER)

Operating time knob (T)

Alarm indicator

Terminal block 

(See notes 1 and 2.)

Terminal block 

(See notes 1 and 2.)

0.1

Item

Meaning

Power indicator
(PWR: Green)

Lit when power is being supplied (see note).

Relay status indicator
(RY: Yellow)

Lit when relay is operating (normally lit).

Alarm 
indicator

Overvoltage:
Red

Lit when there is an overvoltage.
The indicator flashes to indicate the error status after 
the overvoltage has exceeded the threshold value 
while the operating time is being clocked.

Undervoltage:
Red

Lit when there is an undervoltage or phase loss.
The indicator flashes to indicate the error status 
after the undervoltage has exceeded the threshold 
value while the operating time is being clocked.

Lit when there is a phase sequence error.

Item

Usage

Overvoltage knob 
(OVER)

Can be set between 

30% and 25% of the rated 

input.

Undervoltage knob 
(UNDER)

Can be set between 

30% and 25% of the rated 

input.

Operating time knob (T) Used to set the operating time to 0.1 to 30 s.

For 2.5 mm

2

 or 

smaller solid wires

For ferrules with 
insulating sleeves

8 mm max.

8 mm max.

Summary of Contents for K8AB-PM Series

Page 1: ...Legend 1 Basic Model K8AB Measuring and Monitoring Relays 2 Functions PM Three phase Phase sequence Phase loss Relay Simultaneous upper and lower monitoring 3 Rated Input Voltage 1 115 127 133 138 20...

Page 2: ...oss 0 1 s max Startup lock time LOCK 1 s or 5 s Switched using DIP switch Indicators Power PWR Green Relay output RY Yellow OVER UNDER Red Output relays Two SPDT relays NC operation Output relay ratin...

Page 3: ...time Fluctuation based on measured value at standard temperature 20 C to standard temperature 10 max Standard temperature to 60 C 10 max Humidity 25 to 80 Humidity influence Operating value Based on a...

Page 4: ...L1 L2 L3 T T Note 1 The K8AB PM output relay is normally operative 2 The power ON lock prevents unnecessary alarms from being generated during the instable period when the power is first turned on Th...

Page 5: ...or Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 0 1 Item Meaning Power indicator PWR Green Lit when power is being supplied see note Relay status indicator RY Yellow Lit when rela...

Page 6: ...ch Settings The power ON lock time number of wires and rated voltage are set using the DIP switch located on the bottom of the Unit Load Voltage input Signal output 14 12 L1 L2 L3 11 L1 N L2 L3 Signal...

Page 7: ...urn the knob while there is an input to the input terminals until the alarm indicator flashes when the set value and the input have reached the same level Use this as a guide to set the voltage The ra...

Page 8: ...in accident or corruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use th...

Page 9: ...just the slide resistor so that the voltage applied to the K8AB terminals is 120 of the set value for overvoltage detection and 80 of the set value for undervoltage detection when the auxiliary relay...

Page 10: ...operation As the graph shows phase loss cannot be detected because the motor terminal voltage does not drop very much even if a phase is lost when the load on the motor is light To detect motor load...

Page 11: ...Cat No N146 E1 02 Three phase Phase sequence Phase loss Relay K8AB PM 11...

Page 12: ...TIAL DAMAGES LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED ON CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY In no event shall the responsibil...

Reviews: